Carrier 52MQAU12301AA Package Unit Air Conditioner

Installation and Operating Instructions - Page 6

For 52MQAU12301AA.

PDF File Manual, 24 pages, Read Online | Download pdf file

52MQAU12301AA photo
Loading ...
Loading ...
Loading ...
6
ELECTRICAL DATA
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death and/or property damage
DO NOT alter cord or plug or use an extension cord.
!
WARNING
POWER CONNECTION OPTIONS
Appro pri at e power cord acces so ry ki t is d et erm i ned
by the voltage, and amperage of the branch circuit.
Th e un i t d o es n ot come with a po wer co rd (or
hard wire kit). An accessory power cord k i t m us t
be ordered t o connect the unit to the outlet. If the
uni t is to be hard wired, an access ory hard wire kit
must be ordered.
IMPORTANT: For 265V units, if power cord
accessory option is selected, the cord is only 18”
long and must plug into the accessory electrical
265V subbase.
Be sure that your outlet matches the appropriateblade
confi g u rat i on of the p l u g and t h at it is wit h i n reach of
the s ervi ce cord .
All wi ri n g, in clu d i ng in s t al lat i o n of th e receptacl e,
mus t be in accordance wi t h the NEC an d l ocal codes,
ordinances and regulations. National codes require
the us e o f an arc faul t or leak age current det ect io n
device on all 208/230V power cords. Be sure to select
the correct cord for your installation.
ALL UNITS
Wire Size
Use recommended wire size given in Table 1 and
install a single branch circuit. All wiring must
comply with local and national codes. All units are
des i gn ed to o p erate off O NE s i n g le b ranch ci rcui ts
only.
NOTE: Use copper conductors only.
Table 1—SUGGESTED BRANCH CIRCUIT WIRE SIZES*
NAMEPLATE AMPS
AWG WIRE SIZE{
7.0 to 12 14
12.1 to 16 12
16.1 to 24 10
LEGEND
AW G --- A m e r ic a n W i r e G a u g e
* Single circuit from main box.
{ Based on copper wire at 60_C temperature rating.
Grounding
For safety and protection, the unit is grounded
through the service cord plug or through separate
ground wire provided on hard wired units. Be sure
that the branch circuit or general purpose outlet is
grounded.
VOLTAGE SUPPLY
Check voltage supply at outlet. For satisfactory
results, the voltage range must always be within the
ranges found on the data i nformation plate.
Cord--connected
Units
The 250-- v field supplied outlet must match the plug
for t he s tandard 208/230 --v unit s and be withi n reach
of th e servi ce cord . The st an dard co rd--con n ect ed
265 --v uni ts requi re an access o ry elect ri cal subbase
for operat i o n. Refer t o Table 2 f or proper recept acl e
and fuse type.
Power Cord
Protection
The power cord for 230/208v units provide power
cord fire p rot ect i on . Unit power automatically
disconnects when unsafe conditions are detected.
Power to the unit can be restored by pressing the reset
buttononplughead.
Upon completion of unit installation for 230/208V
models, an operational check should be performed
using the TES T/RESET buttons on the plug head.
NOTE: The 265v models do not incorporate this
feature as they require use of the electrical subbase
accessory.
Table 2—RECEPTACLES AND FUSE TYPES -- 250, 265 VOLTS
RECEPTACLE
AMPS 15 20 30 15 20 30
RATED VOLTS 250 250 250 265 265 265
T I M E --- D E L A Y T Y P E F U S E
(or HACR Circuit Breaker)
15 20* 30 15 20 30
LEGEND
HACR --- Heating, Air Conditioning, Refrigeration
* May be used fro 15--- amp applications
Downloaded from www.ManualsFile.com manuals search engine