FLOOR PROTECTOR
This heater must have a non-combustible oor protector
with an R-Value of at least 1.4 installed beneath it if the
oor is constructed of combustible material. If a oor pad
is used, it should be UL listed or equal. The oor protector
should be large enough to extend under the stove and
beyond each side as indicated. If there is a horizontal run
of ue pipe, there needs to be oor protection under it that
extends two inches beyond either side of the pipe. The
oor protector should exceed the stove as shown:
REAR
FRONT
SIDE SIDE
Front 22” (559 mm)
Sides 8” (204 mm)
Rear *2” (51 mm)
*Canadian Installations require
8” (204 mm) to the rear.
CLEARANCES TO COMBUSTIBLES
It is of utmost importance that the clearances to
combustible materials be strictly adhered to during
installation of the stove.
If there is a horizontal run of ue pipe there must be at
lease 18” of clearance between the pipe and the ceiling.
There also has to be oor protection under the horizontal
run that extends 2” beyond each side of the ue pipe.
Floor to ceiling height must be at least 7’ (2.13m) in all
cases.
Do not place any combustible material within 4’ (1.2m)
of the front of the unit.
The clearance between the ue pipe and a wall are valid
only for vertical walls and for vertical ue pipe.
The chimney connector must not pass through an attic
or roof space, closet or similar concealed space, a oor,
or a ceiling.
For Canadian installations, where passage through a
wall, or partition of combustible construction is desired,
the installation must conform to CAN/CSA-B365.
A ue pipe crossing a combustible wall must have a
minimum clearance of 18” (458 mm).
To reduce ue clearances from combustible materials,
contact your local safety department.
D
B
A
C
E
F
E
Single Wall Pipe (Double Wall Pipe)
Key in mm
A 15 (12) 381 (305)
B 18 (18) 458 (458)
C 19 (16) 483 (407)
D 29 (29) 737 (737)
E 12 (12) 305 (305)
F 22 (22) 559 (559)
OUTSIDE COMBUSTION AIR
Your wood stove is approved to be installed with an
outside air intake (4FAK) which is necessary for a mobile
home. This type of installation is also required in air tight
houses and houses with negative pressure problems. You
can purchase this option through your heater dealer. Make
sure to specify the part number mentioned in this booklet.
Installation instructions are supplied with the air intake kit.
Outside combustion air may be required if:
INSTALLATION