Figure 33 System types available (each option provides factory presets for operating parameters)
SYSTEM TYPE presets
System Type
8-Character
Abbreviation
3-Character
Abbreviation
Supply
Max °F
Max Blr
Temp °F)
OD Reset
Min °F
Supply
Min °F
OD Reset
Max °F
Run
Boiler
Pump
Run System
Pump/Aux
Fan-coil FAN-COIL
FCL 180 180 0 140 70 YES YES
Finned Tube
Baseboard
FIN BASE
FTB 180 180 0 130 70 YES YES
Cast Iron Baseboard IRONBASE
CIB 180 180 0 120 70 YES YES
Cast Iron Radiators RADIATOR
CIR 180 180 0 120 70 YES YES
Radiant - slab on grade RAD SLAB
RSG 120 120 0 80 70 YES YES
Radiant - thin slab RAD SLAB
RTS 140 140 0 80 70 YES YES
Radiant - below floor
(staple up)
RADFLOOR
RSU 160 160 0 90 70 YES YES
Radiant - above floor
(sleeper system)
RADFLOOR
RAF 140 140 0 90 70 YES YES
Domestic Hot Water DOMESTIC
DHW 180 180 N/A N/A N/A NO NO
Custom (user defined)
XXXXXXXX
(user input)
first three
of user
input
180 180 0 70 70 YES YES