ELECTRICAL CONNECTION
PERMANENT CONNECTION (HARD WIRING)
US only, for Canada it is mandatory to connect the range
by using cordset with plug supplied.
z
Units may be hard wired to the power supply. The
installer must provide approved flexible aluminium
conduit, 3/4" (19mm) trade size, maximum 6ft (1.8m)
long. Locate the terminal block on the rear of the unit and
remove access cover.
z
The strain relief bracket orientation must be
switched in order to accommodate for a permanent
wiring connection:
1 Remove the factory supplied power cord with plug.
2 Remove the 2 screws on the bracket.
3 Re-secure bracket with the 2 screws so that the 1 1/8"
(29mm) smaller opening is facing down.
z
The conduit must be installed to the terminal block using
an approved conduit connector. The free end of the
conduit must be connected to a junction box provided in
the electrical supply zone.
z
Mount a strain relief (not provided) into the 1 1/8" (29mm)
diameter hole located below the terminal block. Wiring
for the unit is to be brought into the terminal block
through the conduit and through the strain relief. Make
suitable connections to the terminal block provided.
z
Installer — Show the owner the location of the circuit
breaker. Mark it for easy reference.
4-Wire Connection
1 Loosen the L1 (black), L2 (red) and neutral (white) screws.
2 Mount the conduit fitting to the 1 1/8" (29mm) hole in the
strain relief bracket.
3 Secure the neutral (white) power lead to the center
terminal and tighten the screw.
4 Secure the L1 (black) and the L2 (red) power leads to the
terminals immediately to the left (L1) and right (L2) of the
neutral terminal. Tighten the screws.
5 Secure the Ground (green) lead to the green screw
located to the right of the terminal block using the
supplied cupped washer. The end of the grounding
conductor must be retained by the cupped washer.
6 Check all connections are securely tightened.
7 Reinstall the Terminal Block cover.
3-Wire Connection (using supplied Ground lead)
1 Loosen the L1 (black), L2 (red) and neutral
(white) screws.
2 Mount the conduit fitting to the 1 1/8" (29mm) hole
in the strain relief bracket.
3 Secure the supplied Ground (green) lead to the
grounding screw to the right of the terminal block.
4 Secure the Neutral (white) power lead together with
the free end of the Ground (green) lead to the center
terminal. Tighten the screw.
5 Secure the L1 (black) and the L2 (red) power leads to
the terminals immediately to the left (L1) and right (L2)
of the neutral terminal. Tighten the screws.
6 Check all connections are securely tightened.
7 Reinstall the Terminal Block cover.
PENL1 L2
NL1 L2
PE
1 23
Terminal Block
Strain relief bracket
123
Smaller opening