Rinnai 8 Portable Room AC OIM
8. Repairtointrinsicallysafecomponents
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed 
the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only 
types that can be worked on while live in the presence of a ammable atmosphere. The test apparatus shall be at 
the correct rating. Replace components only with parts specied by the manufacturer. Other parts may result in the 
ignition of refrigerant in the atmosphere from a leak.
9. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other 
adverse environmental e󰀨ects. The check shall also take into account the e󰀨ects of aging or continual vibration 
from sources such as compressors or fans.
10. Detectionofammablerefrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant 
leaks. A halide torch (or any other detector using a naked ame) shall not be used.
11. Leakdetectionmethods
The  following  leak  detection  methods  are  deemed  acceptable  for  systems  containing  ammable  refrigerants. 
Electronic leak detectors shall be used to detect ammable refrigerants, but the sensitivity may not be adequate, 
or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the 
detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment 
shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and 
the appropriate percentage of gas (25 % maximum) is conrmed. Leak detection uids are suitable for use with 
most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with 
the  refrigerant  and  corrode  the  copper  pipe-work.  If  a  leak  is  suspected,  all  naked  ames  shall  be  removed/ 
extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, 
or isolated (by means of shut o󰀨 valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) 
shall then be purged through the system both before and during the brazing process.
12. Removalandevacuation
When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall 
be used. However, it is important that best practice is followed since ammability is a consideration. The following 
procedure shall be adhered to:
Remove refrigerant;  Purge the circuit with inert gas; Evacuate;  Purge again with inert gas; Open the  circuit by 
cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be ushed with 
OFN to render the unit safe. This process may  need to be  repeated several times.  Compressed air or  oxygen 
shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and 
continuing to ll until the working pressure is achieved, then venting to atmosphere, and nally pulling down to a 
vacuum. This process shall be repeated until no refrigerant is within the system.
When the nal OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to 
take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that 
the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.
13. Chargingprocedures
In  addition  to  conventional  charging  procedures,  the  following  requirements  shall  be  followed.  Ensure  that 
contamination of di󰀨erent refrigerants does not occur when using charging equipment. Hoses or lines shall be as 
short as possible to minimise the amount of refrigerant contained in them.
Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
Label the system when charging is complete (if not already).
Extreme  care  shall  be  taken  not  to  overll  the  refrigeration  system.  Prior  to  recharging  the  system  it  shall  be 
pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. 
A follow up leak test shall be carried out prior to leaving the site.
SAFETY & IMPORTANT INFORMATION