Start Up Conditions
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a closed
system, the volume of water will grow. As the volume of water
grows, there will be a corresponding increase in water pressure
due to thermal expansion. Thermal expansion can cause
premature tank failure (leakage). This type of failure is not
covered under the limited warranty. Thermal expansion can also
cause intermittent temperature-pressure relief valve operation:
water discharged from the valve due to excessive pressure build
up. The temperature-pressure relief valve is not intended for the
constant relief of thermal expansion. This condition is not covered
under the limited warranty.
A properly-sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion. Thermal expansion tanks are available from Sears
stores and through the Sears Service Centers. Contact the local
plumbing inspector, water supplier and/or the Sears Service
Center regarding the installation of a thermal expansion tank.
Table 2: Thermal Expansion Tank Speci cations
Tank Dimensions Pipe
Model Capacity
in Inches Fitting
Number In Gallons Diameter Length On Tank
153.331020 2 8 (203 mm) 12-3/4 (323 mm) 3/4” Male
153.331050 5 11 (279 mm) 14-3/4 (375 mm) 3/4” Male
Table 3: Expansion Tank Sizing Chart
Inlet* Water Heater Capacity (Gallons)
Water
Pressure 30 40 50 66 82
Expansion 40psi 2 2 2 5 5
Tank 50psi 2 2 2 5 5
Capacity 60psi 2 2 5 5 5
Needed 70psi 2 2 5 5 5
80psi 2 5 5 5 5
*Highest recorded inlet water pressure in a 24 hour period or
regulated water pressure.
NOTE: Expansion tanks are pre-charged with a 40 psi air
charge. If the inlet water pressure is higher than 40 psi, the
expansion tank’s air pressure must be adjusted to match
that pressure, but must not be higher than 80 psi.
FIGURE 43.
STRANGE SOUNDS
Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not represent
harmful or dangerous conditions.
Operational Conditions
SMELLY WATER
In each glass-lined water heater there is installed one anode
rod (see parts section) for corrosion protection of the tank.
Certain water conditions will cause a reaction between this rod
and the water. The most common complaint associated with the
anode rod is one of a “rotten egg smell.” This odor is derived
from hydrogen sul de gas dissolved in the water. The smell is
the result of four factors which must all be present for the odor
to develop:
A. A concentration of sulfate in the supply water.
B. Little or no dissolved oxygen in the water.
C. A sulfate reducing bacteria within the water heater. (This
harmless bacteria is non-toxic to humans.)