Kenmore 153326362 water heater

User Manual - Page 14

For 153326362.

PDF File Manual, 32 pages, Download pdf file

Loading ...
Loading ...
Loading ...
14
11. Replace the access panel.
FIGURE 21.
12. Complete wiring to the water heater, or if completed, turn
“ON” electric power to the water heater after lling the tank
with water.
FIGURE 22.
Never use this water heater unless it is completely full of water.
To prevent damage to the tank and heating element, the tank
must be lled with water. Water must ow from the hot water
faucet before turning “ON” power.
Wiring
You must provide all wiring of the proper size outside of the
water heater. You must obey local codes and electric company
requirements when you install this wiring.
If you are not familiar with electric codes and practices, or if you
have any doubt, even the slightest doubt, in your ability to connect
the wiring to this water heater, obtain the service of a competent
electrician. Contact your Sears salesperson to arrange for a
professional electrician.
WATER HEATERS EQUIPPED FOR ONE VOLTAGE ONLY:
This water heater is equipped for one type voltage only. Check
the rating plate near the bottom access panel for the correct
voltage. DO NOT use this water heater with any voltage other
than the one shown on the model rating plate. Failure to use the
correct voltage can cause problems which can result in DEATH,
SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. If you
have any questions or doubts consult your electric company.
If wiring from your fuse box or circuit breaker box was aluminum
for your old water heater, replace it with copper wire. If you wish
to reuse the existing aluminum wire, have the connection at the
water heater made by a competent electrician. Contact your
Sears salesperson to arrange for a professional electrician.
1. Provide a way to easily shut off the electric power when
working on the water heater. This could be with a circuit
breaker or fuse block in the entrance box or a separate
disconnect switch.
2. Install and connect a circuit directly from the main fuse or
circuit breaker box. This circuit must be the right size and
have its own fuse or circuit breaker. Refer to the chart in the
Product Speci cations section for the correct size wire and
fuse or circuit breaker.
3. If metal conduit is used for the grounding conductor:
a. The grounding electrode conductor shall be of copper,
aluminum, or copperclad aluminum. The material
shall be of one continuous length without a splice or
joint.
b. Rigid metal conduit, intermediate metal conduit, or
electrical metallic tubing may be used for the grounding
means if conduit or tubing is terminated in ttings
approved for grounding.
c. Flexible metal conduit or flexible metallic tubing
shall be permitted for grounding if all the following
conditions are met:
The length in any ground return path does not
exceed 6 feet (1.82 m).
The circuit conductors contained therein are protected
by overcurrent devices rated at 20 amperes or less.
The conduit or tubing is terminated in ttings approved
for grounding.
For complete grounding details and all allowable exceptions,
refer to the current edition of the NEC - National Electrical Code
NFPA 70.
4. A standard 1/2” conduit opening has been made in the water
heater junction box for the conduit connection.