16
(B) Denition and description of SW03
SW03_1-8 is used to set indoor unit address on system. Set address only if using central controller YCZ-A004. Leave
default if no central controller is used.
Note:
Set the address by code when connecting the centralized controller or gateway or charge system.
Address of centralized controller=communication address+0 or+64.
SW03_ 2=OFF, address of centralized controller=communication address+0=communication address
SW03_ 2=ON, address of centralized controller=communication address+64 (applies when centralized controller is
used and there are more than 64 indoor units)
SW03_1
Address setting
mode
[1] Address setting mode
0 Automatic setting (default)
1 Code-set address
SW03_2
~
SW03_8
Code-set indoor
unit address
and centralized
controller address
[2] [3] [4] [5] [6] [7] [8] Address of indoor unit
Address of centralized
controller
0 0 0 0 0 0 0 0# (Default) 0# (Default)
0 0 0 0 0 0 1 1# 1#
0 0 0 0 0 1 0 2# 2#
0 1 1 1 1 1 1 63# 63#
1 0 0 0 0 0 0 0# 64#
1 0 0 0 0 0 1 1# 65#
1 0 0 0 0 1 0 2# 66#
1 1 1 1 1 1 1 63# 127#
Electrical Wiring
Function switches
For other wired remote controller settings, please refer
to controller manual.
The difference between master and slave wired controller
Comparison
item
Master
wired
controller
Slave wired controller
Function
All
function
1.ON/OFF, Mode, Fan speed, Temp,
Setting, Swing, Energy saving, Clock
function, Mode Setting, Screen Saving
and Child lock are available.
2.Cancel the lter cleaning icon.
3.Look up the detailed parameter and
malfunction code.
DIP
switch
On/Off
station
Function
Default
setting
Sw1
On Slave wired controller
Off
Off Master wired controller
Sw2
On Ambient temp. display on
Off
Off Ambient temp. display off
Sw3
On
Collect ambient temp. from
PCB of indoor
Off
Off
Collect ambient Temp. from
wired controller
Sw4
On Non-volatile memory invalid
Off
Off Non-volatile memory valid
Sw5
On Old protocol
Off
Off Self adaption
Sw6
On reserved
Off
Off reserved
Sw7
On
Model with Up/Down and
Left/Right swing
Off
Off Model with Up/Down swing
Sw8
On Fresh Air unit
Off
Off General unit
Dip Switch Setting of YR-E17 Wired Controller