Troubleshooting (continued)
฀ Troubleshooting suggestions — ฀฀฀฀฀
Faults
Display Condition Diagnostics Corrective Action(s)
Configuration fault Conguration data in the
control safety micro does
not match that in the
control’s application micro.
Correct the invalid conguration
information.
Reconrm all settings within the Control Settings screen.
Cycle power to the unit.
Perform a factory reset by going to Diagnostics – Control
Settings – Factory Default Reset and follow the on-
screen instructions.
DHW Outlet > Boiler Out *Combi Only*
DHW Outlet > Boiler Outlet
+ 10°F and burner has been
ring for at least 30 seconds.
Clears when the DHW Outlet
sensor < Boiler Outlet sensor plus
7°F.
Ensure appropriate water ow is being delivered by the
installed circulators.
Check appropriate valves are open.
Check 3-way valve is operating correctly.
Internal Clock Fault Occurs when the internal
clock of the control is out
of sync.
Clears when the control sees
a valid clock count within the
control.
Cycle power of the boiler.
Check the wiring of the display.
If problem persists, replace display.
Supply 60F > Return Occurs if either Boiler Out
temperatures are greater
than Boiler In temperature
by more than 60F or the
burner has been on for less
than 2 minutes.
If this condition occurs when
the burner has been on for
more than 2 minutes, the
burner stops ring but no
message or lockout occurs.
The rst time a lockout occurs,
the time to clear is 2 minutes
30 seconds. The second time a
lockout occurs it’s a 3 minutes 30
second lockout. The third time, its
4 minutes 30 seconds, the fourth
time its 5 minutes 30 seconds.
The fth time its 6 minutes 30
seconds.
The system will retry, indenitely,
every 6 minutes 30 seconds as
long as the temperatures return
to being < 60 degrees.
If the burner rst for at least 2
minutes without the temperature
dierence exceeding 60 degrees,
the time condition for the >
60 degree soft lockout is reset
back to the minimum value of 2
minutes 30 seconds.
Ensure proper water ow is present through boiler.
Ensure circulators are sized correctly per the system
installation and are installed correctly.
Check wiring to circulators.
For Combi applications, add a pre-pump time to the
Combi priority to mix and circulate water to reduce
chances of this fault occurring.
Temperature Sensor
Flue 1 Sensor Open
Flue 1 Sensor Short
Flue 2 Sensor Open
Flue 2 Sensor Short
Boiler Out 1 Sensor Open
Boiler Out 1 Sensor Short
Boiler Out 2 Sensor Open
Boiler Out 2 Sensor Short
Boiler In Sensor Open
Boiler In Sensor Short
Specied sensor is sensed as
Open/Short.
Clears automatically when sensor
is no longer Open/Short.
Check for loose or damaged wires on the designated
sensor and at the control board.
Replace appropriate sensor.
If issues persist, replace control.
Blower Fault 1 Blower does not reach
zero RPM within 4 minutes
when mode is Standby or
Prepump.
Clears automatically after 1 hour. Check for loose or disconnected low voltage wires
to blower motor. Inspect low voltage blower motor
harness.