Connect wiring — general information (continued)
Figure฀18 Blocked vent shutoff switch installation
Part number 550-142-330/0421
27
SGO
OIL-FIRED NATURAL DRAFT STEAM BOILER — SERIES 4 — Boiler Manual
SERVICE฀TECHNICIAN฀ONLY฀—฀read฀and฀follow฀completely.
Blocked vent shutoff switch
Electric shock hazard – Turn off electri-
cal power supply at service entrance panel
before making any electrical connections to
avoid possible electric shock hazard. Failure
to do so can cause severe personal injury
or death.
In Canada, a blocked vent shutoff switch
kit must be installed (see replacement parts
list page 42). See Figure 28.
When using the OVD damper kit, the
BVSS is required, and is integrated into the
damper harness wiring.
When using the BVSS without the OVD
damper, the BVSS is wired directly to the
junction box as follows.
The BVSS wiring diagram in Figure 24, page 31 shows
boiler wiring up to the burner disconnect. For addi-
tional information, refer to manufacturer’s installation
instructions.
After฀installing฀BVSS฀switch,฀proceed฀as฀follows
1. Disconnect power.
2. Install BVSS Switch Wiring Harness (P/N 591-391-
942, which is included in BVSS kit P/N 591-624-650)
as follows:
a. Remove cover from BVSS Box.
b. Install straight fitting end of the harness on the
BVSS Box. Install elbow (90º) end fitting on the
Boiler Junction Box (see Figure 18).
c. Install both the fork ends to the screw terminals
on the BVSS Switch as per the wiring diagram,
(see Figure 21, page 29).
d. Replace BVSS box cover.
To฀wire฀blocked฀vent฀shutoff฀switch,฀see:
Figure 19, page 28 for float-type LWCO
Figure 22, page 30 for probe-type LWCO