General piping information
•฀Hartford Loop piping arrangement and wet return are required for
steam boilers.
•฀Maintain 24-inch minimum from waterline to bottom of header
(minimum 50
7
/8" from floor or top of foundation).
•฀When using condensate receiver, feed pump must be energized by
boiler-mounted pump control.
•฀Use swing joints in steam piping.
•฀If installation is to comply with ASME or Canadian requirements, an
additional pressure limit control is needed. Install control between
existing pressure control and pressure gauge. Control must be installed
with siphon (supplied with boiler) between control and boiler. Set
control to minimum of 5 psi above set point of existing control and
maximum setting of 15 psi. Wire as shown on boiler wiring diagram.
Install piping
1. See Table 5 at right and Figure 14, page 21 or Figure 15, page 22.
Improperly piped systems or undersized piping can con-
tribute to erratic boiler operation and possible boiler
or system damage. Piping system must be installed as
shown, using minimum pipe sizes shown. Consult your
Weil-McLain distributor or sales office before installing
alternate piping.
2. Install relief valve vertically in “R” tapping on back of boiler. See
Figure 14 or Figure 15 and also refer to tag attached to relief valve for
manufacturer’s instructions.
Pipe relief valve discharge line near floor close to floor drain
to eliminate potential of severe burns. Do not pipe to any
area where freezing could occur. Do not plug, valve or place
any obstruction in discharge line.
3. Float-type low water cutoff only — install blow down line in bottom
of cutoff. See Figure 14 or Figure 15 and also refer to low water cutoff
manufacturer’s instructions for details.
Pipe blow down line near floor close to floor drain to eliminate
potential of severe burns. Do not pipe to any area where freez-
ing could occur. Do not plug, valve or place any obstruction
in discharge line.
To connect SGO boilers to indirect-fired water
heaters
Install and wire per water heater manual provided with water heater.
If boiler already has a tankless heater installed:
•฀Remove tankless heater and install cover plate.
OR
•฀Leave tankless heater installed. Drain coil and remove piping. Do not
plug holes in tankless heater front plate.
Connect steam piping
Table 5 Steam piping size table
One฀and฀two-pipe฀systems
Boiler฀
Model฀
Number
Riser฀Pipe฀
Size฀฀
(Note฀1)
Header฀
Pipe฀Size฀
“H”
(Note฀2)
Equalizer฀
Pipe฀฀
Size฀
“J”
AB
SGO-3
2½"
(Note฀3)
2½” 1½"
SGO-4
2½"
(Note฀3)
2½" 1½"
SGO-5 2½" 3" 1½"
SGO-6 2½" 2½" 3" 1½"
SGO-7 2½" 2½" 3" 1½"
SGO-8 2½" 2½" 3" 1½"
SGO-9 2½" 2½" 3" 1½"
One-pipe฀counter฀ow฀systems
SGO-3 2½" 2½” 1½"
SGO-4 2½" 2½" 1½"
SGO-5 2½" 3" 1½"
SGO-6 2½" 2½" 4" 1½"
SGO-7 2½" 2½" 4" 1½"
SGO-8 2½" 2½" 4" 1½"
SGO-9 2½" 2½" 4" 1½"
Note฀1
Based on ASHRAE Fundamentals
Handbook recommendations, allowing ½
oz. pressure drop at 0 psig.
Note฀2
Based on ASHRAE Fundamentals
Handbook recommendations, allowing 2
oz. pressure drop per 100 feet of pipe at 3.5
psig. Maintain minimum 24" height from
waterline to bottom of header.
Note฀3
Can be reduced to 2".
Part number 550-142-330/0421
20
SGO
OIL-FIRED NATURAL DRAFT STEAM BOILER — SERIES 4 — Boiler Manual
SERVICE฀TECHNICIAN฀ONLY฀—฀read฀and฀follow฀completely.