GAS-FIRED WATER BOILER – 80/110/150/199 BOILER MANUAL
ECO
Tec Control / Priority settings
Available control settings and system presets
options
Default
setting
COMBI
default
UNITS
ASSIGNED INPUTS
1, 2, 3, 4, 0-10V, FLOW - FLOW -
See System Type Presets OFF 1=COMBI DHW -
SYSTEM SUPPLY,
BOILER OUT, DHW
OUT
SYSTEM SUPPLY if
detected, Boiler Out
if not
DHW OUT -
Outdoor Temp, 0-10V,
none
Outdoor Temp (If
attached)
None -
See System Type Presets
See System Type
Presets
N/A
°F
See System Type Presets N/A 120 °F
See System Type Presets
See System Type
Presets
N/A
°F
ON, OFF N/A ON -
50 - 100 70 N/A °F
-20 to 49 0 N/A °F
5.0 - 10.0 10.0 N/A V
0.0 - 4.9 0.0 N/A V
OFF, 1 - 240 OFF N/A M
5 - 15 10 N/A °F
DHW OFF DIFF
1 - 20 N/A 10 °F
5 - 30 10 N/A °F
DHW ON DIFF
1 - 20 N/A 1 °F
See System Type Presets
See System Type
Presets
See System Type Presets °F
2 - 15 5 5 °F
2 - 30 5 5 °F
0 - 150 50 50 °F
MAX ON TIME
OFF, 1 - 240 30 30 M
MIN ON TIME
OFF, 1 - 240 15 N/A M
OFF, Economy,
High Performance
Economy OFF -
70 - 180 N/A 120 (Econ), 140 (H. Perf) °F
1 - 30 N/A 30 (Econ), 10 (H. Perf) °F
1 - 30 N/A 10 (Econ), 5 (H. Perf) °F
1 - 30 N/A 10 °F
ECO BOOST
OFF, ON N/A ON -
ECO BOOST SETPOINT
70 - 180 N/A 130 °F
ECO BOOST ON DIFF
1 - 30 N/A 10 °F