Designer Series Direct Vent Gas Fireplace
The maximum number of 45° elbows permitted per side
wall installation is two (2). These elbows can be installed
in either the vertical or horizontal run.
For each 45° elbow installed in the horizontal run, the
length of the horizontal run MUST be reduced by 18"
(457 mm). This does not apply if the 45° elbows are
installed on the vertical part of the vent system.
The maximum number of elbow degrees in a system is
270°. Figure 24

Figure 28 -
Maximum Vent Run with Elbows
FP2838
A + B = 17' Maximum
Horizontal 90° Elbow =
3' Reduction
7'6"
10'
7'
1
2
3
4
1
2
3
4
Figure 29 -
Maximum Elbow Usage
1 + 2 + 3 + 4 = 270°
FP2307


 

Cut a 12Z\x"H x 10Z\x" W
hole through the interior wall.
Cut a 10Z\x"H x 10Z\x"W
square hole through the exterior wall frame. Figure 25
Hole opening should be 8Z\x"
(216 mm) in diameter.
2. The center of the hole should line up with the center line
of the horizontal rigid vent pipe end. Allow 1/4" minimum
rise per foot. Figure 30
B\,

        




B\,

B\, 

 

      





10Z\x
(267 mm)
Min.
Fireplace Hearth
Framing Detail

8Z\x
(216 mm)
Fireplace Hearth
FP2293
Figure 30 -
Locate vent opening on wall
10Z\x
(267 mm) Min.