Series 2 Wall Mount Gas-fired Water Boiler Boiler Manual
37 Troubleshooting(continued)
Figure 123฀฀฀฀฀
Configuration mode
By pressing the DHW- and DHW+ push buttons together for 10 seconds, it is possible to enter into the Configuration mode.
The display starts with showing b01 blinking. By means of the CH “+” and CH “-” push buttons it is possible to select the
parameters; between b01 and b28. Selecting one of these parameters, by means of the DHW “+” and DHW “-” push buttons
it is possible to adjust his value (not flashing). The value is automatically saved.
By pressing the DHW- and DHW+ push buttons together for 10 seconds, it is possible to leave the Configuration mode.
If no action has been taken, the MMI automatically leaves this mode after 2 minutes.
Parameter Description Default Note
b01 Gas type selection (0Natural Gas, 1LPG) 0
b02
DHW conguration
2Storage tank,
3Instantaneous with secondary heat exchanger,
2 - Heating Only
3 - Combi
b03 Water pressure protection (0Switch, 1Sensor) 0
b04 Fan absolute DHW maximum speed (Hz)
See
Figure 128, page 101.
b05 Fan absolute CH maximum speed (Hz)
See
Figure 128, page 101.
b06 Fan absolute minimum speed (Hz)
See
Figure 128, page 101.
b07 Not implemented - DHW cong. 2
DHW maximum output boost/limit level (%) - DHW cong. 3
--
100
DHW conf. dependent
Do Not Adjust
b08 Not implemented - DHW cong. 2
DHW maximum output boost/limit time (Sec) - DHW cong. 3
--
60
DHW conf. dependent
Do Not Adjust
b09 Fan offset low level (Hz) 10 Do Not Adjust
b10 Summer/Winter function (0Sum/Win, 1always Win) 1 Do Not Adjust
b11 Variable input switch functionality (Number) 4 Do Not Adjust
b12 Variable output relay functionality (Number)
See
Figure 128, page 101
Model dependent
b13 External pcb variable output relay functionality (Number) 7 Do Not Adjust
b14 Hours of no DHW ow to set the Economy mode (Hours) 24 Range0-24 hours
b15 Fault F20 function (0disable, 1enable) 0 Do Not Adjust
b16 Maximum exhaust gases temperature (°F) 200
200 PVC/ 212 CPVC
sel. dependent
b17 Main supply frequency (050Hz, 160Hz) 1 Do Not Adjust
b18
Not implemented - DHW cong. 2
Not implemented - DHW cong. 3
--
--
DHW conf. dependent
Not used,
Do Not Adjust
b19 DHW tank prepare mode (Num.) - DHW cong. 2
DHW ow sensor lter (Sec) - DHW cong. 3
0
0
DHW conf. dependent
Do Not Adjust
b20 Fan type selection (0Not used, 1EBM) 1 Do Not Adjust
b21 Pump protection time (Sec) 5 Do Not Adjust
b22 PVC/CPVC/Polypro/AL29-4C Selection 1 See Options on page 34
b23 PVC maximum temperature (°F) 190 Do Not Adjust
b24 CPVC maximum temperature (°F) 200 Do Not Adjust
b25 Pre-purge time between A01 attempts 0 Do Not Adjust
b26 High altitude & Chimney length selection 0 Do Not Adjust
b27 Hydraulic conguration - DHW cong. 2
Not implemented - DHW cong. 3
0
--
DHW conf. dependent
Do Not Adjust
b28 Offset ame current low limit 20 Do Not Adjust