Series 2 Wall Mount Gas-fired Water Boiler Boiler Manual
29 Standard Altitude
Figure 97 ฀฀฀
()
Standard Altitude Boiler Adjustment

1. Press DHW- and DHW+ buttons together for 10 seconds
to enter the parameter setup menu. The standard values for
parameter “b04”, b05 and b06, are shown in Table.
2. Roll down the menu by pressing the CH button until the
parameter “b04 is on the screen.
3. Set parameter b04 to parameter in Table.
4. Repeat steps 2 and 3 above to also adjust parameter b05
and “b06, according to Table.
5. Press DHW- and DHW+ buttons together for 10 seconds
to leave the menu. The values are automatically saved.
The Ignition speeds are the same for Standard
and High Altitude, theres no need to change.
In USA Input rates are derated 4% for each 1000
ft. above sea level, beyond 2000 ft. in accordance
with National Fuel Gas Code, ANSI Z223.1/NFPA
54 – latest edition, and/or the Natural Gas and
Propane Installation Code, CAN/CSA B149.1.
For elevations above 10,000 feet, please contact
Weil-McLain Technical Support for details.
In Canada, Input rates are derated 10% for altitudes
of 2000 ft. to 4500 ft. above sea level. Please use
appropriate Fan Speed Settings for High Altitude
provided in the following pages of this manual.
In Canada for elevation beyond 4500 feet. Please
consult Provincial Authorities having jurisdiction
and/or local codes.
Perform Boiler Manual Start-up
Follow all instructions in the start-up section
for boiler start-up after converting for High
Altitude. Because the boiler has been changed,
you must verify correct operation, including
checking combustion with test instruments
both at high fire and low fire as described in
the this manual, pages 81, 82 & 83.
Check the correct ignition sequence of the
boiler after the conversion, as in page 90.
Failure to comply could result in severe per-
sonal injury, death or substantial property
damage.
Model
Standard Altitude
฀฀
Low
Fire
(b06)
Ignition
(Can't
Change
- Needs
PC)
High Fire
In
CH Mode
(b05)
High Fire
In
DHW
Mode
(b04)

35 80% 155 155

35 80% 145 145

40 60% 200 200

40 60% 185 185

39 50% 210 210

40 50% 220 220