GE AZ61H12EABW2 Zoneline® Deluxe Series Heat Pump Unit, 265 Volt

Owner's Manual and Installation Instructions - Page 7

For AZ61H12EABW2. Series: Zoneline® Deluxe Series

PDF File Manual, 120 pages, Read Online | Download pdf file

AZ61H12EABW2 photo
Loading ...
Loading ...
Loading ...
GE,4ppliances.com
[ MODE 7 I DuctMode
The default setting for Mode 7 is OFF,
Thissetting is used when the unit is installed using a
duct adapter kit, If the unit is ducted, the Duct Mode
needs to be set to ON,This increases the fan speed to
ensure proper circulation,
Press MODEuntil a 7 appears in the first digit of the
display, Pressthe up or down arrow keys to set this
switch to OFF"LJ" or ON "rs ,"This is shown in the
second digit of the display, PressAUXSETto confirm
your selection and exit AUXSETmode,
For Model AZ6100, press MODE to continue setting
other functions, Pressing MODEon Model AZ4100 will
return you to AUXSETmode and an "AU" will appear in
the display,
DuctMode OFF Duct Mode ON
[ MODE 8 All-Electric Heat (AZ6100 only)
The default setting for Mode 8 is OFF,
Thiselectric heat option functions only on the 6100
model, When this option is ON "r'l," heat pump
operation is locked out, causing the unit to provide
only electric resistance heat,
To set All-Electric Heat option, press MODEuntil an 8
appears in the first digit of the display, Pressthe up or
down arrow keys to set this switch to OFF"u" or
ON "r s," This is shown in the second digit of the display,
PressAUXSETto confirm your selection and exit AUXSET
mode,or pressMODEto continue setting other functions,
All-Electric
Heat OFF
All-Electric
HeatON
[ MODE 9 Heat Boost (AZ6100 only)
The default setting for Mode 9 is OFF,
When Heat Boost is ON and outer temperatures are
between 25°Fand 46°F,heat pump only operation is
locked out, This setting is used to provide supplementary
heat to the heat pump operation by electric resistance
heat in conditions where the heat pump-only operation
is not sufficient to maintain a consistent, comfortable
room temperature, NOTE:Temperature Boost option
should not be used with remote thermostat operation,
Thiswill cause the unit to switch to resistance heat when
the outdoor temperature is 46°F,
To set Heat Boost, press MODEuntil a 9 appears in the
first digit of the display, Pressthe up or down arrow keys
to set this switch to OFF" LJ" or ON "r'l ," This is shown
in the second digit of the display, PressAUXSETto
confirm your selection and exit AUXSETmode,
9U 92
HeatBoostOFF Heat BoostON
Auxiliary Controls-- Terminal Connections
The auxiliary controls are located behind the room
cabinet beneath the access cover,
r-_ Turn off and unplug the unit,
F_ Remove the room cabinet, Seethe ToRemove the
Room Cabinetsection,
]Remove the screw from the access cover,
To make wiring connections, insert the wires into the
bottom of the terminals and tighten screws securely,
"_ fter all
replace
The owner is responsible for making all connections and
setting the appropriate AUXSETmode,
A CAUTION:
Improper wiring may damage the Zoneline electronics,
No common busing is permitted, Damage or erratic
operation may result, A separate wire pair must be run
from each separate controlling switch to each individual
Zoneline,
desired connections have been made, _ it
the access cover and room cabinet,
_Cover _ _ _ _ _
3@@8£@/_ ,x_