Installation Instructions
265 VOLT ELECTRICAL CONNECTION OPTIONS
,& WARNING:
Connection of this 265 V AC product to a branch circuit
MUSTbe done by direct connection in accordance with
the National Electrical Code, Plugging this unit into a
building-mounted exposed receptacle is not permitted
by code,
These models must be installed using the appropriate
GE power supply kit for the branch circuit amperage and
the electrical resistance heater wattage desired, Use the
POWER CONNECTION CHART on page 16 to determine
the correct kit required, One of the following installation
methods (A or B) must be used,
A. FORSUBBASEINSTALLATION
Electrical subbase kits are available to provide a flexible
enclosure for direct connection,
Branch Circuit and Proper GE Power
Unit Amperage Rating Subbase Kit Supply Kit
15 RAK204E15 RAK5172
20 RAK204E20 RAK5202
30 RAK204E30 RAK5302*
*Not approved for use on 7000 BTU models,
The instructions provided with the selected subbase kit
must be carefully followed, It is the responsibility of the
installer to ensure the connection of components is done
in accordance with these instructions and all electrical
codes,
i
B. FOR DIRECTCONNECT
INSTALLATION
If an electrical subbase is not used, direct connection to
branch circuit wiring inside the provided junction box must
be done in accordance with the following steps,
Order the following Kit for 265-volt direct connection
as required:
Branch Circuit and Power
UnitAmperage Rating Supply Kit
15 RAK5157
20 RAK5207
30 RAK5307*
_Notapproved for useon7000BTUmodels,
Proceed to the "MAKEELECTRICALCONNECTIONTOTHE
UNIT"section,
NOTE: Order Kit RAK4OO2CWto enable a quick
disconnect inside the junction box,
i
14