Weil-McLain AQUABALANCE COMBI AB-120C Series 2 High-efficiency Gas Water Boiler

User Manual - Page 68

For AQUABALANCE COMBI AB-120C.

PDF File Manual, 136 pages, Read Online | Download pdf file

AQUABALANCE COMBI AB-120C photo
Loading ...
Loading ...
Loading ...
Part number 550-100-325/0419
68
AquaBalance
®
Series 2 Wall Mount Gas-fired Water Boiler Boiler Manual
Figure 95 ฀฀฀
120 Figure 96 ฀฀฀
155
28 DHW Settings (Combi Only)
(continued)
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
9
9.5
10
10.5
11
11.5
12
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100105
AquaBalance 120 - DHW PRODUCTION
G.P.M.
Delta T (ºF)
AquaBalance 120
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
9
9.5
10
10.5
11
11.5
12
12.5
13
13.5
14
14.5
15
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
Freestyle 155 - DHW PRODUCTION
Freestyle 155
Delta T (ºF)
G.P.M.
AquaBalance 155
AquaBalance 155 -
The “D” Parameter codes below are part of the normal Control Operation and typically appear during Start Up.
This a Timed” or Auto Recycle event.
฀D1….the boiler is / has finished the call for Domestic Water heating, and is in the transition to either
standby mode or central heating mode.
฀D2….the boiler has reached the required water set point, and the firing has stopped / with a call for Cen-
tral Heating still applied by the T-Stat to the boiler. Circulators will continue to operate and the boiler is
monitoring the two internal water sensors (return & discharge) waiting for a water “Delta-T to return…at
that time the boiler will re-fire if need be.
฀D3….the boiler has made 3 tries for ignition and has failed to ignite. A re-trial ignition cycle / delay is in
effect for 3 more tries to ignite/restart boiler operation.
Parameter Description
D1
After cycle of Domestic water mode, D1 will be displayed.
D2
When required boiler water set - point is reached D2 will be displayed.
D3
After an attempt for ignition, re-trial ignition delay is in effect (D3 is displayed).
* Check for proper fuel supply.
* Remove and check ignitor for proper gap, 5/32”, replace if disgured, check combustion setting Natural gas or LP.
* Insure condensate is draining properly.
* Insure venting size and length are correct and unobstructed.