51
AquaBalance
®
Series 2 Wall Mount Gas-fired Water Boiler Boiler Manual
21 Gas piping (continued)
฀฀
1. See page 14 for gas line sizing information.
฀฀฀฀฀฀
1. See Figure 64 for location of the gas inlet pressure test port.
฀฀฀฀฀฀

1. Set up the boiler to operate at maximum rate as described in
section “ Test mode” Figure 104, page 79.
2. With the boiler operating at maximum rate check that the op-
erational (working) gas pressure at the inlet gas pressure test
port (see above) complies with the requirements of Table 2 .
3. Ensure that this inlet pressure can be obtained with all other
gas appliances in the property working.
Measure the gas rate
Measure the gas rate and check against following Table 2:
For natural gas or liquefied petroleum (propane) gas, the pres-
sure required at gas valve inlet pressure port (verify minimum
gas pressure when all gas appliances are in operation):
a. Maximum: 13” w.c. with no flow (lockup) or with boiler
on.
b. Minimum: 3.5” w.c. gas pressure, with gas flowing (verify
during boiler startup, while boiler is at high fire)
c. Nominal gas pressure: 11.0” w.c.
4. Install 100% lockup gas pressure regulator in supply
line if inlet pressure can exceed 13” w.c. at any time.
Adjust lockup regulator for 13” w.c. maximum.
Figure 64 
฀฀
Gas Rate 

Combi
Boiler
model
Maximum rate Minimum rate
ft
3
/h ft
3
/h
AB-80
 
AB-120
 
AB-155
 
Table 2 