INSTALLATION (cont.)
LCDI Power Cord Instruction
WARNING: This LCDI power cord is a non-serviceable device.
Attempting to open the device may expose the user to the hazards
of electric shock, and could void warranties of this product.
Manufacture’s reliability is limited to the replacement of the device.
CAUTION:
Read the attention printed on the device for proper use and handling
of this device.
This device is used for monitoring leakage current.
Do not immerse in water.
This device must only be plugged into an appropriate wall outlet. Do
not remove the ground prong.
In the event that this device trips, the cause of malfunctions should
be corrected first before further use.
Using the device beyond the recommended voltage poses risk to
users.
Conductors inside this cord are surrounded by shields, which
monitor leakage current.
These shields are not grounded, and they are periodically examined
for any damage.
Do not use this product in the event the shields become exposed.
Do not repeatedly push TEST and/or RESET buttons.
Test Procedure
Test this device once when the power supply is installed to assure proper
operation.
1. Plug into the grounded power receptacle.
2. If POWER light is not on, press RESET button once. Light should turn on.
3. Press TEST button once, POWER light must turn off.
4. Press RESET button once again for use. POWER light should turn on.
5. If this test fails, do not use this device. Contact a qualified technician for
details.
Reset Button
Test Button
<Front View>
ILL00965-00