installation manual
10. WIR
Connect the connective cables to the terminals as identified
with their respective mached numbers on the terminal block
of indoor and outdoor units.
Re-install the cover or the protection board.
10.1
Connect the cable
10.2
The Specification of Power
10.3
Wiring figure
(Refer to Table10-1Table 10-8)
(Refer to Fig.10-3Fig.10-6)
Remove the electric cover of the outdoor unit.
If there is no cover on the outdoor unit, disassemble
the bolts f rom the maintenance boa rd and remove the
protection board. (See Fig. 10.1, 10.2)
Cover
Screw
Fig. 10.1
Protection Board
Fig. 10.2
NOTE:
Remark per EMC Directive 2004/108/EC.
For to prevent flicker impressions during the start of the
compressor (technical process), following installation conditions
do apply.
1. The power connection for the air conditioner has to be done at
the main power distribution. The distribution has to be of a low
impedance, normally the required impedance reaches at a 32 A
fusing point.
2.. No other equipment has to be connected with this power lin
3.. For detailed installation acceptance please refer to your pow
supplier, if restrictions do apply for products like washing
machines, air conditioners or electrical ovens.
4.. For power details of the air conditioner refer to the rating pla
of the product.
5.. For any question contact your local dea r.
The appliance shall be installed in accordance with national
wiring regulations.
The air conditioner should use separate power supply with
rated voltage.
The external power supply to the air conditioner should
have ground wiring, which is linked to the ground wiring
of the indoor and outdoor unit.
The wiring work should be done by qualified persons
according to circuit drawing.
An all-pole disconnection device which has at least 3mm
sepaaration distance in all pole and a residual current
device (RCD) with the rating of above 10mA shall be
incorporated in the fixed wiring according to the national
rule.
Be sure to locate the power wiring and the signal wring
well to avoid cross-disturbance.
Do not turn on the power until you have checked carefully
after wiring.
The power cord type designation is H07RN-F.
I.. Whether the air conditione heats well in the case of the
HEATING/COOLING type.
2) The outdoor unit
a.. Whether there is vibration or abnormal noise duri
operation.
b. Whether the generated wind, noise, or condensed of by
the air conditioner have influenced your neighborhood.
c.. Whether any of the refrigerant is leake
A protection feature prevents the air conditioner from being
activated for approximately 3 minutes when it is restarted
immediately after shut off.
CAUTION
1) The indoor unit
a.. Whether the switch on the remote controller works wel
b.. Whether the buttons on the remote controller wor
well.
c.. Whether the air flow louver moves normal .
d.. Whether the room temperature is adjusted wel
e.. Whether the indicator lights normal .
f.. Whether the temporary buttons works wel
g.. Whether the drainage is norma
h.. Whether there is vibration or abnormal noise duri
operation.
4
According to the user's requirement, install the remote
controller frame where the remote controller's signal can
reach the indoor unit smoothly.
Test operation
Set the air conditioner under the mode of "COOLING" with
the remote controller, and check the following points. If there
is any malfunction, please resolve it according to the chapter
"Troubleshooting" in the "Owner's Manual".
11.. TEST OP TION
The test operation must be carried out after the entire
installation has been completed.
Please confirm the following points before the test operation:
2
1
3
The indoor unit and outdoor unit are installed properly.
Tubing and wiring are correctly completed.
The refrigerant pipe system is leakage-checked.
The drainage is unimpeded.
The heating insulation works well.
The ground wiring is connected correctly.
The length of the tubing and the added stow capacity of
the refrigerant have been recorded.
The power voltage fits the rated voltage of the air
conditioner.
There is no obstacle at the outlet and inlet of the outdoor
and indoor units.
The gas-side and liquid-side stop valves are both opened.
The air conditioner is pre-heated by turning on the power.