Unit Mounting Dimensions
Clearance Drawing for Outside Installation
Install the Connection Pipe
1. Aim the counter-bore of the connecting pipe at
the stop valve and tighten the taper nut with
fingers. Then tighten the taper nut with a torque
wrench to the correct specification mentioned on
pg. 10.
2. When extending the pipe, an extra amount of
refrigerant must be added so that the operation
and performance of the air conditioner will not be
compromised.
NOTE: This table is for reference only.
INSTALLATION: OUTDOOR UNIT
14
Piping Length
≤ 16.4ft.
CC ≤ 12000 BTU 20g/m
CC ≥ 18000 BTU 30g/m
16.4ft. - 49.2ft.
Not Needed
Amount of Refrigerant to be Added
Stop Valve
Taper Nut
Connecting Pipe
Spanner
Gas Side Pipe
Liquid Side Pipe
W1
W2
A
B
NOTE: All measurements should be no less than posted from obstructions.
11.8 in
7.9 in
11.8 in
NOTE: Technique to measure distance does not
change between unit design versions.
Unit
BTU
Outdoor Unit Size
W1(W2)*H*D (in. ")
A (in. ")
B (in. ")
12K BTU
28.74(30.4)*21.46*11.22 21.1 10.9
18K BTU 30.90(33.5)*21.90*11.8 21.1 12.7
24K BTU 32.48(34.3)*25.79*12.2 24.6 13.7
Installation Outdoor Unit Bolt