62 | APPLICATION
Single-Zone LGRED° Four-Way Ceiling-Cassette System Engineering Manual
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
PLACEMENT CONSIDERATIONS
Indoor Unit
Do’s
Select a location for installing the indoor units that will meet the
following conditions:
Place the unit where air circulation will not be blocked.
Locate the indoor unit in a location that is level, and where it can be
easily connected to the outdoor unit.
Place the unit in a location where condensation drainage can be
conveniently routed away.
Include enough space around the indoor unit so that it is accessible
for maintenance and service purposes.
Place the unit in a location where electrical noise / electromagnetic
waves will not impact operation. Maintain proper distances between
the indoor units and electric wires, audio and visual appliances,
breaker / circuit panels, etc.
Place in an area that is level and with enough strength to bear the
weight of the indoor unit(s).
Do Not’s
No obstacles to air circulation around the unit; keep proper distances from ceilings, doorways, floor, walls, etc.
The unit should not be installed near a heat or steam source, or where considerable amounts of oil, iron powder, or flour are used.
The unit should not be installed where sulfuric acid and flammable or corrosive gases are generated, vented into, or stored.
Avoid installing the unit near high-frequency generators or near any equipment that generates an electromagnetic field (minimum 3-1/3 feet
away).
7KHXQLWVKRXOGQRWEHLQVWDOOHGZKHUHVXOIXULFDFLGDQGÀDPPDEOHRUFRUURVLYHJDVHVDUHJHQHUDWHGYHQWHGLQWRRUVWRUHG7KHUHLVULVNRI¿UH
explosion, and physical injury or death.
Selecting the Best Location for the Indoor Unit
WARNING
Figure 41: 2 x 2 Cassette Ceiling Opening Dimensions and Bolt
Locations.
Figure 42: 3 x 3 Cassette Ceiling Opening Dimensions and Bolt
Locations.
Figure 40: Indoor Unit Clearance Requirements.
“A”
19-11/16
or more
19 -11/16
or more
11 -13/16
or less
39-3/8
or more
Ceiling Cassette
Ceiling Board
13/32
or more
Ceiling beam or
other obstruction
Floor
Unit: Inch
Ceiling
WALL
A” =
Ceiling Board
Any objects in room
(cabinets, furniture, etc.)
Below 36 kBtu: At least 70 - 7/8; no more than 11 ft., 9-23/32 in.
Over 36 kBtu: At least 70 - 7/8; no more than 13 ft., 9-11/32 in.
23-1/16 (585) ~ 26 (660) (Ceiling Opening)
23-1/16 (585) ~ 26 (660) (Ceiling Opening)
Panel Size: 27-9/16 (700) x 27-9/16 (700)
Unit: Inch (mm)
20-3/8 (517)
18-1/8 (461)
20-3/8 (517)
20-9/16 (523)
22-7/16
(570)
22-7/16
(570)
12-9/16
(319)
34-7/16 (875) (Ceiling Opening)
34-7/16 (875) (Ceiling Opening)
30-15/16 (787)
(Hanging Bolt)
26-15/16 (684)
Panel Size: 37-3/8 (950) x 37-3/8 (950)
Unit: Inch
(
mm
)
26-7/16 (671)
33-1/16 (840)
Unit Size
33-1/16 (840)
Unit Size