36 | PRODUCT DATA
Single-Zone LGRED° Four-Way Ceiling-Cassette System Engineering Manual
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
ELECTRICAL CONNECTIONS
Figure 29: General Four-Way Ceiling Cassette System Power / Communications System Schematic (Appearances May Vary).
Controller Options
Single Zone LGRED Four-Way Ceiling Cassette systems include a wireless handheld remote controller
(18,000 Btu/h models Model No. PQWRHQ0FDB; Part No. AKB73757604 for 18,000 Btu/h cassette
indoor units; Part No. AKB75735404 for 24,000 to 48,000 Btu/h cassette indoor units). Optional
LG-suppled wired controllers are available. See “Functions, Controls, Options”, or contact an LG
representative for more information.
Wireless Handheld Remote Controller features:
Display Panel: Displays operation conditions.
On / Off Buttons: Turns system operation on and off.
Mode Button: Selects the operation mode: Cooling, Heating, Auto, Dry (Dehumidification), or Fan.
Temp Up / Down Buttons: Adjusts the desired room temperature in the different modes.
Fan Speed Button: Sets desired fan speed.
Reset: Initializes the handheld remote control settings.
Wired Controller Connections
Optional controllers (see “Functions, Controls, Options”, or contact an LG representative for more
information) can connect to the Four-Way Ceiling Cassette indoor unit in one of two different ways.
1. LG Wired Remote Extension Cable with Molex plug (PZCWRC1; sold separately) that connects to the
CN-REMO terminal on the indoor unit PCB.
2. Field-supplied controller cable that connects to the indoor unit terminal block (must be at least
UL2547 or UL1007, and at least FT-6 rated if local electric and building codes require plenum cable
usage). Communication cable from indoor unit to remote controller(s) is to be 22 AWG, 3-conductor,
twisted, stranded, unshielded. Wiring must comply with all applicable local and national codes.
Use a conduit for the communications cable / power wiring from the outdoor unit to the indoor units.
Make sure the communications cable / power wiring from the outdoor units to the indoor units, and the power wiring to the outdoor unit are
separate, otherwise, the outdoor unit operation will be affected by electrical noise and will malfunction or fail.
Figure 30: PQWRHQ0FDB
(AKB73757604) Wireless Hand-
held Remote Controller for 18,000
Btu/h Cassette Indoor Units.
L
L
N
N
G
Power Supply
Main Switch
Circuit Breaker
Fuse
Power Wiring
(Including Ground)
Outdoor Unit
1(L1)
or
L(L1)
2(L2)
or
N(L2)
Terminal Block Outdoor
3
Terminal Block Outdoor
Communication
Cable
Terminal Block Indoor
3
Power
Wiring
Indoor Unit
1(L1)
or
L(L1)
2(L2)
or
N(L2)
1(L1) or
L(L1)
2(L2) or
N(L2)