Table 2 FE4A/FE5A Fan Coil Airflow Delivery Chart (CFM) Electric Heating Models
MODEL F E 4A OUTDOOR UNIT CAPACITY BTUH
ELECTRIC HEATER kW RANGE
5 9 10 15 20 24 30
002
EMERGENCY
18,000
24,000
30,000
36,000
625
625
650
800
975
625
625
725
875
975
675
675
775
875
975
775
900
925
1025
950
1125
1125
003
EMERGENCY
24,000
30,000
36,000
42,000
675
675
800
975
1125
700
875
875
975
1125
775
875
875
1025
1125
850
1100
1100
1150
1150
1050
1150
1150
1250
1350
005
EMERGENCY
30,000
36,000
42,000
48,000
675
800
975
1125
1305
700
875
975
1125
1305
775
875
1025
1125
1305
850
1100
1150
1150
1305
1050
1150
1250
1250
1350
1400
1500
1425
1600
006
EMERGENCY
36,000
42,000
48,000
60,000
1050
1050
1125
1300
1625
1050
1050
1125
1300
1625
1050
1100
1150
1300
1625
1050
1350
1350
1350
1625
1125
1350
1350
1500
1750
1750
1750
1750
1750
1750
1750
MODEL F E 5A OUTDOOR UNIT CAPACITY BTUH
ELECTRIC HEATER kW RANGE
5 9 10 15 20 24 30
004
EMERGENCY
24,000
30,000
36,000
42000
675
975
1050
1050
1125
775
975
1050
1050
1125
775
975
1100
1100
1150
900
1125
1350
1350
1125
1350
1350
Note 1: E mer gency - Air conditioner with electric heater application, or emergency heat.
Note2: TheseairflowsareminimumairflowsasULlisted.
Note 3: Dashed entry indicates that the heater/fan coil/outdoor unit combination is not approved. Do not apply.