OUTSIDE BACK EXHAUST (EXAMPLE ONLY)
The following chart describes an example of one possible ductwork installation.
NOTE: Align the exhaust with the space between the studs, or the wall should be prepared at the
time it is constructed by leaving enough space between the wall studs to accommodate the
exhaust.
Exhaust connection
The hood exhaust has been designed to mate with a standard 3 1/4"x10" rectangular duct. If a round
duct is required, a rectangular-to-round transiting adaptor must be used. Do not use less than a 6"
diameter duct.
NOTE: It is important that venting be installed using the most direct route and with as few elbows as
possible. This ensures clear venting of exhaust and helps prevent blockages. Also, make
sure dampers swing freely and nothing is blocking the ducts.
Maximum duct length
For satisfactory air movement, the total duct length of 3 1/4"x10" rectangular or 6" diameter round
duct should not exceed 140 feet.