Loading ...
Loading ...
Loading ...
PRODUCT DATA | 13
Product Data
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
Nominal
Tons
Unit Model
No.
Hertz Voltage
Voltage
Range
(Min. to Max.)
MCA MOP
Compressor
Quantity
Compressor
Motor RLA
Locked
Rotor
Amps
Outdoor Unit
Fan Motor
Indoor Unit Fan
Motor
W FLA W. FLA
Cooling Heating
2 x 2 Four-Way Ceiling Cassettes
1-1/2 LC188HHV4 60 208 - 230 187 - 253 22 30 1 14.5 14.5 23 460 x 1 1.6 x 1 170 0.6
3 x 3 Four-Way Ceiling Cassettes
2 LC249HHV
60 208 - 230 187 - 253
22 30
1
14.5 14.5 23 460 x 1 1.6 x 1 170 0.6
3 LC369HHV
32 40 22 22 33 280 x 2 1.6 x 2
230 1.0
3-1/2 LC429HHV
260 1.3
4 LC489HHV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Table 4: Electrical Data.
ELECTRICAL DATA