GENERAL DATA
Table 3: Single-Zone LGRED Four-Way 3 x 3 Ceiling Cassette System General Data.
EEV: Electronic Expansion Valve, IDU: Indoor Unit, ODU: Outdoor Unit. Unit comes with a dry helium
charge.
This data is rated 0 ft above sea level, with 24.6 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb
(WB); and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb
(WB); and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1
Power Input is rated at high speed.
2
Power wiring to the ODU is field supplied, solid or stranded, and must comply with the applicable local
and national codes.
3
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A
refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5
All power wiring/communication cables from ODU to IDU are field supplied and are to be minimum 14
AWG, 4-conductor, stranded, shielded or unshielded (if shielded, must be grounded to chassis at ODU
only), and must comply with applicable local and national codes.
6
Piping lengths are equivalent.
7
Cooling range can be extended from 5°F down to -4°F using the Low Ambient Wind Baffle Kit (sold
separately).
System (Model) (Indoor Unit / Outdoor Unit)
LC249HHV
(LCN249HV/
LUU240HHV)
LC369HHV
(LCN369HV/
LUU360HHV)
LC429HHV
(LCN429HV/
LUU420HHV)
LC489HHV
(LCN489HV/
LUU480HHV)
Ceiling Grille Model Number (Sold Separately) PT-AAGW0 PT-AAGW0 PT-AAGW0 PT-AAGW0
Cooling Capacity (Min ~ Rated ~ Max) (Btu/h)
9,600~24,000~30,000 14,400~36,000~46,000 16,800~42,000~49,000 19,200~ 48,000~53,000
Cooling Power Input
1
(kW)
0.48~1.905~3.00 0.72~2.858~5.410 0.93~3.28~5.50 1.09~3.84~5.82
Heating Capacity (Min ~ Rated ~ Max) (Btu/h)
10,800~27,000~33,000 16,000~40,000~46,000 18,000~48,000~57,600 19,000~52,000~61,000
Heating Power Input
1
(kW)
0.57~2.25~3.80 0.80~3.20~4.70 1.17~3.405~5.80 1.40~3.85~6.20
COP @47°F
3.51 3.66 4.13 3.95
Maximum Heating Capacity (Btu/h)
Outdoor 17°F (WB)/Indoor 70°F (DB)
29,100 42,100 51,400 55,100
Outdoor 5°F (WB)/Indoor 70°F (DB)
27,000 40,000 48,000 52,000
Outdoor 0°F (WB)/Indoor 70°F (DB)
25,560 37,760 45,200 47,410
Outdoor -4°F (WB)/Indoor 70°F (DB)
24,410 35,970 42,970 43,740
Outdoor -13°F (WB)/Indoor 70°F (DB)
21,610 30,000 35,990 35,980
EER
12.60 12.60 12.80 12.50
SEER
21.00 21.50 19.50 17.50
HSPF
10.20 11.00 11.60 11.70
Power Supply V, Ø, Hz
2
208-230 / 1 / 60
Outdoor Unit Operating Range
Cooling (°F DB)
5 to 118
7
Heating (°F WB)
-13 to +64
Indoor Unit Operating Range
Cooling (°F WB)
57 to 77
Heating (°F DB)
59 to 81
Indoor Temperature Setting Range
Cooling (°F DB)
60 to 86
Heating (°F DB)
60 to 86
Unit Data
Refrigerant Type
3
/ Refrigerant Control
R410A / EEV
IDU Sound Pressure Levels ±1 dB(A) (Mx/H/M/L/SL)
4
48 / 40 / 37 / 35 / 32 55 / 44 / 42 / 41 / 40 56 / 46 / 43 / 41 / 39 56 / 46 / 43 / 41 / 39
ODU Sound Pressure Level ±1 dB(A) (Cool/Heat)
4
51 / 52 52 / 54 54 / 56 54 / 56
Indoor Unit Net / Shipping Weight (lbs.)
45.2 / 54.9 55.8 / 67.7 59.5 / 70.5 59.5 / 70.5
Outdoor Unit Net / Shipping Weight (lbs.)
133.4 / 144.4 198.9 / 223.1 210.9 / 234.1 210.9 / 234.1
Grille Net / Shipping Weight (lbs.)
15.6 / 20.5 15.6 / 20.5 15.6 / 20.5 15.6 / 20.5
Power Wiring / Communications Cable (No. x AWG)
5
4 x 14
Compressor (Type x Qty.)
R1 Scroll x 1
Dehumidification Rate (pts./hr.)
3.80 7.10 7.27 9.74
Fan
Indoor Unit Type x Qty. / Outdoor Unit Type x Qty.
Turbo x 1 / Axial x 1 Turbo x 1 / Axial x 2
Motor / Drive
Brushless Digitally Controlled / Direct
Airflow Rate
Indoor Unit (Cooling, Max / H / M / L [CFM])
794 / 671 / 600 / 530 1,200 / 971 / 883 / 794 1,483 / 1,130 / 953 / 812
Outdoor Unit (CFM)
2,048 4,238
Piping
Liquid (in.)
Connection Size
3/8 Flare
Pipe Size
3/8 Flare
Vapor (in.)
Connection Size
5/8 Flare
Pipe Size
5/8 Flare
Condensate Drain O.D. / I.D. (in.)
1-1/4 / 1
Additional Refrigerant Charge (oz./ft.)
0.43
Minimum / Maximum Pipe Length (ft.)
16.4 / 164 16.4 / 246
Piping Length
6
(no additional refrigerant, ft.)
24.9
Maximum Elevation Difference (ft.)
98.4