Loading ...
Loading ...
Loading ...
www.usaprocom.com
15200159-01B
Figure 12 - Gas Connection
* Purchase the optional CSA design-certied equipment
shuto󰀨 valve from your dealer.
The installer must supply an external regula-
tor. The external regulator will reduce incom-
ing gas pressure. You must reduce incoming
gas pressure to between 11" and 14" of water.
If you do not reduce incoming gas pressure,
heater regulator damage could occur. Install
external regulator with the vent pointing down
as shown in Figure 13. Pointing the vent down
protects it from freezing rain or sleet.
Figure 13 - External Regulator
with Vent Pointing Down
Figure 14 - Gas Regulator Location and
Gas Line Access into Stove Cabinet
External
Regulator with
Vent Pointing
Down
Propane
Supply Tank
Equipment
Shuto󰀨 Valve
Ground
Joint Union
3/8" NPT
Pipe Nipple
Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap
Test Gauge
Connection*
Sediment
Trap
Tee Joint
Pipe Nipple
Gap
3" Minimum
Gas Regulator
Inlet Connector
Install sediment trap in supply line as shown
in Figure 12. Place sediment trap where it is
within reach for cleaning. Place sediment trap
where trapped matter is not likely to freeze.
A sediment trap traps moisture and contami-
nants. This keeps them from going into heater
controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
Natural Gas
From Gas Meter
(5" W.C.** to 9.5"
W.C. Pressure)
Propane
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure)
INSTALLATION
Loading ...
Loading ...
Loading ...