Installation and Operation Manual - Wood Stove
ENGLISH
3.1 Clearances
APPLIANCE CLEARANCES WITH SINGLE
WALL PIPE CONNECTOR
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
Canada USA Canada USA
A 14 ½" (368 mm) 11" (279 mm) A 6" (152 mm) 6" (152 mm)
B 17" (432 mm) 16" (406 mm) B 17" (432 mm) 16" (406 mm)
C 10" (254 mm) 10" (254 mm) C 7" (178 mm) 7" (178 mm)
If the above clearances are met, then the distances measured from the flue outlet will be:
DISTANCES
13
FROM PIPE CONNECTOR
WITH SINGLE WALL PIPE CONNECTOR
DISTANCES¹³ FROM PIPE CONNECTOR
WITH DOUBLE WALL PIPE CONNECTORE
Canada USA Canada USA
D 18" (457 mm) 14 ½" (368 mm) D 9 ¼" (235 mm) 9 ¼" (235 mm)
E 26 ½" (673 mm) 25 ½" (648 mm) E 26 ¼" (667 mm) 25 ¼" (641 mm)
F 19 ¾" (502 mm) 19 ¾" (502 mm) F 16 ½" (419 mm) 16 ½" (419 mm)
13
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances
above mentioned.