Pre-Installation
5.3 Pipework
The pipe runs should be executed as short as possible,
unused pipework should be removed and all remaining
pipework should be lagged in accordance with
regulatory requirements to prevent heat loss and the
formation of condensation.
5.4 Taps and Fittings
        
have a rated operating pressure of 0.6 MPa (6 bar) or
above.
5.5 Risk Assessment
It is strongly recommended to complete a risk
assessment before installing the product. The following
areas require particular consideration in addition to the in-
formation required by the Health and Safety at Work Act.
- Scalding: where appropriate or required by law a

water outlet of the cylinder.
- Explosion: the unit is fully equipped with all relevant
safety equipment to comply with current regulations.

independent third party testing. The correct
application hereafter is the responsibility of the
competent installer.
- Water borne organisms (i.e. Legionella): if applicable
a risk assessment should be carried out following the
recommendations outlined in the Approved Code of
Practice L8.
- The user preference must be considered when
commissioning the system.
5.6 Siting Considerations
When choosing the place where the appliance is to be
installed the following points should be taken into
consideration:
- Structural integrity.
- Access for installation, operation, maintenance and
replacement.
- Routing of discharge pipework.
- Access to water mains supply, hot and cold water
distribution pipework.
- Access to suitable electricity supply.
Particular care must be taken when placing the water
heater in a garage or outbuilding. All exposed pipework
must be correctly insulated to avoid frost damage.
The position and orientation of the water heater should
be such that easy access is provided for servicing the
controls. A minimum distance of 400mm in front of the
immersion is recommended, to allow the replacement
of the immersion heater should the need arise. When
installing the water heater all labels should be clearly
visible and ensure that no pipework hinders any work to
be carried out on the various components.

the appliance is horizontal, see Figure 1.
Figure 1: Correct siting of Water Heater
          
        
weight of the water heater when full of water (please see
technical data) and suitably accessible for
replacement/maintenance without specialist tools or lift-
ing equipment as this will void the warranty
conditions.
Keep the transport bag out of reach of
children (risk of suocation).
- Remove plastic cover and cardboard packaging.
- Remove corner protection pieces, ensuring that all
nails and staples are taken out.


the transport bag.
- Without tilting the appliance, use an appropriate tool
to remove the screws from underneath the pallet.
5.2 Unpacking
It is PROHIBITED:
- To let the appliance operate using air intake which
contains solvents or explosive matter.
- To use air intake which contains grease, dust or
aerosol particles.
- To connect vented exhaust hoods to the ventilation
system.
It is PROHIBITED to install the appliance
- Outdoors
- In rooms which are exposed to frost
- In humid rooms which have a lot of steam or vapour
(for example, a bathroom)