-7-
G
VENT TERMINATION CLEARANCES
A. Minimum 4-feet (1.22m) clearance below or beside any door or window that opens.
B. Minimum 1-foot (0.3m) clearance above any door or window that opens.
C. Minimum 3-feet (0.91m) clearance from any adjacent building.
D. Minimum 7-feet (2.13m) clearance from any grade when adjacent to public walkways.
E. Minimum 2-feet (0.61m) clearance above any grass, plants, or other combustible materials.
F. Minimum 3-feet (0.91m) clearance from an forced air intake of any appliance.
G. Minimum 2-feet (0.61m) clearance below eves or overhang.
H. Minimum 1-foot (0.3m) clearance horizontally from combustible wall.
I. Must be a minimum of 3 feet (0.91m) above the roof and 2 feet (0.61m) above the highest point or the roof
within 10 feet (3.05m).
FIGURE 6
VENT TERMINATION CLEARANCES
Installation