9. FIELD SETTING
9. Field setting
9.1 Outdoor unit DIP switch
DIP Switch Setting of Outdoor Unit (Optional setting)
Turn off all power sources before setting. Without turning off, the switches settings are not
refreshed and might be invalid. Mark of " " indicates the position of DIP switches.
Setting method
24K
36K: SW5-4
60K: S2-4
36K: SW4-3
60K: S1-3
Mandatory
defrost mode
Refrigerant
c
ollection
Mandatory defrost mode
Setting
before
shipment
Normal defrost mode
Setting method
36K/60K
SW1, 2 Setting
Default
Mandatory defrost mode
Refrigerant
collection
Mandatory defrost mode
Operation:
Dial the switch from OFF to ON before turn on the appliance, and set it in heating mode,
then it will run with manual defrosting mode at once.
Refrigerant collection mode
Actions
The compressor runs with the target frequency, and without any protection when frequency
rises; The EEV runs with setting opening; Outdoor unit fan will run with the set fan speed.
Operation procedures:
Step 1:
Press the ON/OFF button to power off the appliance.
Step 2:
Disconnect the machine power.
Step 3:
Close the shut-off valve of the liquid piping with an Allen wrench in a clockwise direction.