Performance data (Cooling operation at rated frequency)
36K outdoor unit matches 36K indoor unit
Outdoor
DB
IWB (°F) 59 63 67 71
IDB (°F) 70 75 80 85 70 75 80 85 70 75 80 85 70 75 80 85
65
TC 30.8 31.1 31.7 32.1 31.7 32.1 32.4 32.8 33.9 34.2 34.5 34.7 \ 41.3 41.6 42.0
S/T 0.99 1.00 1.00 1.00 0.61 0.83 1.00 1.00 0.39 0.57 0.73 0.90 \ 0.39 0.53 0.67
PI 2.16 2.19 2.20 2.20 2.20 2.23 2.24 2.27 2.27 2.29 2.31 2.34 \ 2.86 2.89 2.93
75
TC 30.8 31.2 31.8 32.1 31.8 32.1 32.5 32.9 34.0 34.3 34.6 34.8 \ 40.9 41.2 41.5
S/T 1.00 1.00 0.99 1.00 0.62 0.83 1.00 1.00 0.39 0.56 0.73 0.90 \ 0.39 0.53 0.67
PI 2.40 2.43 2.46 2.46 2.46 2.48 2.51 2.53 2.51 2.55 2.58 2.61 \ 3.16 3.18 3.21
85
TC 30.3 30.7 31.3 31.7 31.3 31.7 32.0 32.3 33.5 33.8 34.1 34.3 \ 40.2 40.5 40.7
S/T 1.00 1.00 1.00 1.00 0.62 0.84 1.00 1.00 0.39 0.57 0.74 0.91 \ 0.39 0.53 0.67
PI 2.71 2.74 2.76 2.76 2.76 2.79 2.82 2.85 2.85 2.88 2.90 2.93 \ 3.58 3.62 3.65
95
TC 29.8 30.1 30.8 31.2 30.8 31.2 31.5 31.8 33.0 33.3 33.5 33.8 \ 39.2 39.6 39.8
S/T 1.00 1.00 1.00 1.00 0.62 0.84 1.00 1.00 0.39 0.57 0.74 0.92 \ 0.39 0.53 0.68
PI 3.25 3.28 3.32 3.32 3.32 3.35 3.39 3.42 3.44 3.47 3.49 3.54 \ 4.26 4.29 4.33
105
TC 29.2 29.6 30.2 30.6 30.2 30.6 30.9 31.2 32.3 32.6 32.9 33.1 \ 37.9 38.0 38.2
S/T 0.99 1.00 1.00 1.00 0.62 0.84 1.00 1.00 0.39 0.57 0.75 0.93 \ 0.39 0.54 0.69
PI 3.87 3.91 3.96 3.96 3.96 4.00 4.04 4.08 4.08 4.12 4.15 4.19 \ 4.94 4.95 4.97
115
TC 26.2 26.5 27.1 27.3 27.1 27.3 27.6 27.9 29.1 29.3 29.4 29.6 \ 31.5 31.7 31.8
S/T 1.00 1.00 1.00 1.00 0.62 0.85 1.00 1.00 0.40 0.60 0.79 0.99 \ 0.39 0.58 0.76
PI 3.94 3.98 4.03 4.03 4.03 4.08 4.12 4.17 4.19 4.22 4.25 4.26 \ 4.39 4.42 4.43
Performance data (Heating operation at rated frequency)
36K outdoor unit matches with 36K indoor unit
ID
OD
72
67 62 57 52 47 42 37 32 27 22 17 12 7
2
-
4
60
TC 44.2 44.2 44.1 44.1 44.0 42.3 38.9 36.0 33.4 33.5 31.5 30.1 28.1 26.1 24.4 22.7
PI 2.98 3.19 3.46 3.75 4.05 4.08 3.93 3.79 3.68 4.05 3.94 3.83 3.70 3.63 3.52 3.45
70
TC 34.2 33.9 34.2 34.1 33.7 33.6 33.6 33.6 32.9 32.9 30.6 29.6 27.6 25.6 24.0 22.3
PI 2.23 2.35 2.59 2.76 2.97 3.23 3.56 3.87 4.02 4.41 4.27 4.15 4.01 3.90 3.78 3.68
75
TC 28.8 28.7 28.7 28.7 28.7 28.7 28.2 28.2 28.2 28.2 28.2 28.1 26.1 24.0 22.0 20.4
PI 1.86 2.00 2.16 2.33 2.55 2.75 2.93 3.20 3.42 3.75 4.04 4.32 4.19 4.06 3.94 3.83
80
TC 23.6 23.6 23.6 23.6 23.5 23.5 23.4 23.4 23.5 23.2 23.2 23.2 23.2 23.2 21.7 20.0
PI 1.55 1.64 1.78 1.93 2.07 2.24 2.41 2.67 2.83 3.01 3.24 3.50 3.78 4.12 4.11 4.00
R
emarks:
TC: Total Cooling Capacity (Gross) kBtu/h
S/T: Sensible Capacity Ratio
PI: Power Input (including the compressor, cond. fan motor) kW
DB: Dry Bulb Temperature