22
GB
6. Electricalwork
6.5.Addresssetting
Switch address setting
Outdoor
Branch Box
M, S, P
Series
Indoor
CITYMULTI
Series Indoor
Address Connection Setting
Switch
tens digit ones digit tens digit ones digit
A B C D E
1 2 3 4 5 6
ON: Indoorconnect
OFF: Noconnection
(SW1-6 not use)
None
tens digit ones digit
SWU2 SWU1 SW12 SW11 SW1 SW12 SW11
Range 51 - 100 1 - 50 1 - 50
Setting
M-Control
Indoor or
Branch Box
address +50
• Accordingtothesetaddress(forexample,01),the
addresses for the connected indoor units are set
sequentially (for example, 02, 03, 04, and 05).
• Specifywhetherindoorunitsareconnectedto
each port (A, B, C, D, and E).
There are
no address
settings for
the indoor
units.
SW1 1 2 3 4 5
ON ON ON ON ON
Port A B C D E
Address
01 (SW11, 12)
02 03 04 05 (sequential numbers)
SW1 1 2 3 4 5 (6)
Port A B C D E not use
IndoorunitsareconnectedON
Indoor units are not connected OFF
Note: 1.Branchboxaddress
Whensettingtheaddress,useanumberwithintherange1–50.
Ex.Thesetaddressis(47)andthereare5indoorunits(A,B,C,D,andE).
IfA:(47),B:(48),C:(49),D:(50),andE:(51),Eisincorrectbecauseitexceeds50.
Ex1.Outdoor+Branch<1>(M,S,PSeriesIndoorA,B,C,D,E)+Branch<2>(M,S,PSeriesIndoorA,B,C)
Outdoor
address
(51) *1
*1 Outdoor address
Branch-Box<1>startaddress+50=01+50=51
*2 Branch-Box<1>
A-port address = Start address = 01
B-port address = Start address + 1 = 02
C-port address = Start address + 2 = 03
D-port address = Start address + 3 = 04
E-port address = Start address + 4 = 05
*3 Branch-Box<2>
Branch-Box<2>startaddress
=Branch-Box<1>oldeststartaddress+1
= 05 + 1 = 06
A-port address = Start address = 06
B-port address = Start address + 1 = 07
C-port address = Start address + 2 = 08
Ex2.Outdoor+Branch<1>(M,S,PSeriesIndoor,C,E)+Branch<2>(M,S,PSeriesIndoorA,C,E)
Outdoor
address
(51) *1
*1 Outdoor address
Branch-Box<1>startaddress+50=01+50=51
*2 Branch-Box<1>
A-port address = Start address = 01
B-port address no connection
C-port address = Start address + 1 = 02
D-port address no connection
E-port address = Start address + 2 = 03
*3 Branch-Box<2>
Branch-Box<2>startaddress
=Branch-Box<1>oldeststartaddress+1
= 03 + 1 = 04
A-port address = Start address = 04
B-port address no connection
C-port address = Start address + 1 = 05
D-port address no connection
E-port address = Start address + 2 = 06
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
M, S, P Series Indoor
(01) = A-port
(02) = B-port
(03) = C-port
(04) = D-port
(05) = E-port
(06) = A-port
(07) = B-port
(08) = C-port
(01) = A-port
non B-port
(02) = C-port
non D-port
(03) = E-port
(04) = A-port
non B-port
(05) = C-port
non D-port
(06) = E-port
Branch-Box<1>
address (01) *2
SW11,3,5 ON
SW1 2, 4 OFF
Branch-Box<2>
address (04) *3
SW11,3,5 ON
SW1 2, 4 OFF
Branch-Box<2>
address (06) *3
SW11,2,3 ON
SW1 4, 5 OFF
Branch-Box<1>
address (01) *2
SW11,2,3,4,5ON
RG79Y960H01.indb 22 2018/02/09 14:31:10