IMPORTANT: the appliance must be installed
following the manufacturer's instructions. The
manufacturer will not be liable for injury to
persons or animals or property damage caused
by an incorrect installation.
5) GAS CONNECTION
The gas connection is located in the rear and on
the right hand underside of these appliances:
24 mm (mod: OCG63FFX - OCG64FFX),
230 mm (mod: OCG95FFX).
There are two ways to carry out the connection to
the main gas line:
A. The hotplate can be connected with rigid pipe
as specified in AS/NZS 5601.
B. If installing with a hose assembly, install with a
hose assembly that complies with AS/ANZ 1869
(Australian Certified), 10 mm ID, class B or D, no
more than 1.2 m long and in accordance with
AS/NZS 5601. Ensure that the hose does not
contact the hot surfaces of the hotplate, oven,
dishwasher or any other appliance that may be
installed underneath or next to the hotplate. The
hose should not be subjected to abrasion, kinking
or permanent deformation and should be able to
be inspected along its entire length with the
hotplate in the installed position.
Unions compatible with the hose fittings must be
used and all connections tested for gas leaks.
The gas supply connection point must be
accessible with the appliance installed..
Warning: ensure that the hose assembly is
restrained from accidental contact with the flue or
flue outlet of an underbench oven.
Natural Gas
Natural Gas installations require the connection of
a gas regulator at the appliance. This regulator is
supplied with the appliance on purchase.
Assemble the regulator (noting the gas flow
direction) and transition pieces (supplied with the
appliance), in accordance with figure 7.
The transition piece on the supply side of the
regulator must be provided by the installer.
Liquified Petroleum Gas.
In a Universal LP Gas installation the gas
regulation is made at the gas cylinder and
regulation at the appliance is not required. To
connect supply to the appliance use transition
pieces as shown in
figure 8. These pieces are supplied with the
appliance on purchase.
WARNING:
THE BURNER FLAME MUST BE ADJUSTED BY
THE INSTALLER.
FAULTY INSTALLATION WILL NOT BE
COVERED UNDER WARRANTY.
THE APPLIANCE IS FACTORY SET FOR
NATURAL GAS. THE TEST POINT PRESSURE
SHOULD BE ADJUSTED TO 1.00kPa WITH THE
WOK BURNER OPERATING AT MAXIMUM.
INSTALLATION
FIG. 7
FIG. 8