34
High Efciency
Single Zone Inverter
Electrical & Refrigeration
Quick Reference
*Minimum Circuit Ampacity
**Maximum Overcurrent Protection
All equipment single phase.
NOTE: All communication cable, including the power wiring cable size must comply
with the applicable local and national code.
PQRCVSL0 PREMTB10U
Wired Wall Thermostat for Single Zone Inverter.
(Applicable to LS307HV2, LS360HV2, LXXXXHSV2, LAXXXHVP and
LSXXXHYV models only)
*** Each system is pre-charged with enough refrigerant to charge 24.6 ft. (41 ft. for LA090HSV2, LA120HSV2, LS091HSV2,
LS121HSV2) of line and the interior unit.
Please choose a proper wire size based on local and state code
Electrical Specifications
Type Model BTU/h Voltage Rated MCA* MOP**
Zone Indoor Outdoor Amps
High Efciency
Art Cool™
Mirror
Single Zone
H/P LA090HSV2 9,000 230/208 230/208 8.5 10 15
H/P LA120HSV2 11,200 230/208 230/208 8.5 10 15
H/P LA180HSV2 18,200 230/208 230/208 17.0 19 30
H/P LA240HSV2 22,000 230/208 230/208 17.0 19 30
High Efciency
Single Zone
H/P LS091HSV2 9,000 230/208 230/208 8.1 10 15
H/P LS121HSV2 11,200 230/208 230/208 8.1 10 15
H/P LS181HSV2 18,200 230/208 230/208 15.4 19 30
H/P LS240HSV2 22,000 230/208 230/208 15.4 19 30
Refrigerant Line Specifications***
Type Model BTU/h Pipe Size Additional Max. Pipe Max.
Zone Liquid Suction Refrigerant Length Elevation
High Efciency
Art Cool™ Mirror
Single Zone
H/P LA090HSV2 9,000 1/4” 3/8” 0.22 oz./ft. 65’ 32’
H/P LA120HSV2 11,200 1/4” 3/8” 0.22 oz./ft. 65’ 32’
H/P LA180HSV2 18,200 3/8” 5/8” 0.38 oz./ft. 98’ 49’
H/P LA240HSV2 22,000 3/8” 5/8” 0.38 oz./ft. 98’ 49’
High Efciency
Single Zone
H/P LS091HSV2 9,000 1/4” 3/8” 0.22 oz./ft. 65’ 32’
H/P LS121HSV2 11,200 1/4” 3/8” 0.22 oz./ft. 65’ 32’
H/P LS181HSV2 18,200 3/8” 5/8” 0.38 oz./ft. 98’ 49’
H/P LS240HSV2 22,000 3/8” 5/8” 0.38 oz./ft. 98’ 49’
Accessory