WARNING: ENCLOSURE REQUIREMENTS FOR BUILT-IN GRILLS AND ACCESSORIES
FOR YOUR SAFTEY
, if not using a Crown Verity propane enclosure for a built-in
application, you must provide the openings listed below for drainage, replacement air
flow and cross ventilation for any storage area exposed to possible leakage from gas
connections, the unit, or propane cylinders:
One side of the gas cylinder enclosure left completely open to the outside or by
providing four (4) ventilation openings. Two (2) openings are to be at the cylinder
valve level (approximately 16 inches (40.6 cm) above the floor) and on opposite walls
of the enclosure. Two (2) more openings must be at the floor level on opposite sides
of the enclosure. The floor level opening must start at the floor and shall extend no
higher than 5 inches (12.7 cm) above the floor. Each opening shall have a minimum of
10 square inches (64.5 cm²) of free area. To achieve the proper ventilation, you may
drill a series of holes, or omit grout from masonry joints, or replace a brick with a
hardware cloth screen. If the floor of the cabinet is raised and the space beneath the
cabinet is open to the outside, the lower ventilation openings may be in the floor.
Doors on any propane enclosure must be non-locking.
The design of the outdoor built-in propane enclosure must provide adequate access so
that the LP gas cylinder can be connected, disconnected, and the connections
inspected and tested outside the cylinder enclosure. Consult you gas supplier for
venting and regulatory requirements when connecting to household propane supply.
DANGER:
A. Never connect a propane appliance to an unregulated propane gas supply
or other gas type.
B. Do not attempt to alter the hose or regulator in any way.
C.
Do not allow the hose to come in contact with any hot surfaces of the grill.
D.
Visually inspect the entire length of the hose assembly before each use for
any evidence of damage (cuts, cracks, burns) or excessive wear. If found,
replace the assembly before using your grill.
E. The connection fitting must be protected when disconnected
from the LP cylinder. If the fitting is allowed to drag on the
ground, damage to the fitting may occur resulting in leaks or an
incomplete connection. Dirt could also enter the small inlet hole,
blocking gas flow completely.