Installation instructions
Installation instructions
Effective January 1, 1996, the National Electrical Code requires that new construction (not
existing) utilize a 4-conductor connection to an electric range.
When installing an electric range in new construction, follow Steps 2 and 3 for 4-wire
connection.
You must use a 3-wire or 4-wire, single-phase A.C. 240 Volt, 60 hertz electrical system.
If the electrical service provided does not meet the above specifications, have a licensed
electrician install an approved outlet.
Use only a 3-conductor or a 4-conductor UL-listed range cord. These cords may be
provided with ring terminals on wire and a strain relief device.
A range cord rated at 40 amps with 125/250 minimum volt range is required.
A 50 amp range cord is not recommended but if used, it should be marked for use with
nominal 1⅜" diameter connection openings. Care should be taken to center the cable and
strain relief within the knockout hole to keep the edge from damaging the cable.
Because range terminals are not accessible after range is in position, flexible service
conduit or cord must be used.
NOTE
If conduit is being used, go to Step 4 on pages 4648.
ALL NEW BRANCH-CIRCUIT CONSTRUCTIONS, MOBILE HOMES, RECREATIONAL
VEHICLES AND INSTALLATIONS WHERE LOCAL CODES DO NOT ALLOW
GROUNDING THROUGH NEUTRAL, REQUIRE A 4-CONDUCTOR UL-LISTED RANGE
CORD.