30
ENGLISH
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Slave1
Outdoor Unit
HR unit
AB
Slave2
Outdoor Unit
3(A) 4(B) 3(A) 4(B) 3(A) 4(B) 3(A) 4(B)
Between Indoor and Master Outdoor unit
• It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units
are matched.(A-A,B-B)
Example) Connection of Communication Cable
[BUS type] [STAR type]
- Connection of communication
cable must be installed like
below figure between indoor
unit to outside unit .
- Abnormal operation can be
caused by communication de-
fect, when connection of com-
munication cable is installed like
below figure(STAR type).
Example) Connection of power and communication cable (UWC)
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm
(1.97inch)
gap
Communication
cable
Main power
terminal block
Insulation sleeves
attachments
Fix firmly not
to be displaced
ODU-IDU
Communication cable
ODU-ODU
Communication cable
Main Power Connection
Communication Connection
CAUTION
It should be wiring power cables or communication cables to avoid
interference with the oil level sensor. Otherwise, That oil level sensor
would be operated abnormally.
!
Checking the setting of outside units
Checking according to dip switch setting
- You can check the setting values of the Master outside unit from the
7 segment LED.
The dip switch setting should be changed when the power is OFF.
Checking the initial display
The number is sequentially appeared at the 7 segment in 5 seconds
after applying the power. This number represents the setting condition.
• Initial display order
• Master Unit • Slave Unit
Dip switch setting Dip switch setting ODU Setting
Slave 1
Slave 2
Order No Mean
8~20
Master model capacity(HP)
10~20
Slave 1 model capacity(HP)
10~20
Slave 2 model capacity(HP)
8~54
Total capacity(HP)
1 Cooling Only
2 Heat Pump
3 Heat Recovery
38 380V model
46 460V model
22 220V model
1 Full function
2 Core function
• Example) ARWB480DAS4
20 14 14 46 3 46 1