49-5000416 Rev. 0 35
Custom Energy Savings Settings
15 – MAXIMUM SETBACK TEMPERATURE - COOL
(72°F - 92°F; 76°F* default setting) Select the “Maximum
Setback Temperature” in °F.
Setback temperature is calculated by measuring HVAC
unit’s ability to attain “Recovery Temperature - Cool”
within “Temperature Recovery Time”.
If recovery is disabled (“Temperature Recovery Time” is
set to “0”) or if setback temperatures have not yet been
calculated, the “Maximum Setback Temperature” value
will be used as the setback temperature for cooling.
If calculated setback temperature for air conditioning is
higher than “Maximum Setback Temperature”, then the
“Maximum Setback Temperature” will be used as setback
temperature for air conditioning.
This feature allows defining the maximum temperature in
a room when room is unoccupied and the thermostat is in
the setback mode.