CONFIGURATION SETTINGS CHART
Configuration Code Description Option Code Description
C1 Interface 0* Chassis Membrane*
rE Wireless Remote
L5 Wired Thermostat
C2 Fan Operation bP Button present
bA* 7-Button, reverts to Cyclic
A Always run fan (even in Off)
bC 7-Button, reverts to Continuous
C3 Reverse Cycle Operation C Cooler Only
H* Heat Pump*
0 Service No Operation "Eo"
C4 Room I.D. Digit 1 & 2 00* - 99 00* - 99
C5 Room I.D. Digit 3 & 4 00* - 99 00* - 99
C6 Wired or Wireless Occupancy 0* Off*
1On
18 18 Hour Automatic Entry
C8 Temp. Limiting Cool 60* - 72 60* - 72
C9 Temp. Limiting Heat 68 - 90, 80* 68 - 90, 80*
Cd English / Metric Temp F* Fahrenheit Scale*
CCelsius Scale
d6 Sensorless Un-Occ. Time 1 - 32, 18* 1 - 32, 18*
d7 1st Un-Occ. Set Back Temp. 1 - 16, 2* 1 - 16, 2*
d8 1st Un-Occ. Set Back Time .1, .5*, 1 - 24 .1 ,.5 ,1 - 24, .5*
d9 2nd Un-Occ. Set Back Temp. 1 - 16, 3* 1 - 16, 3*
dA 2nd Un-Occ. Set Back Time .1, .5, 1* - 24 (d8) - 24, 1*
db 3rd Un-Occ. Set Back Temp. 1 - 16, 6* 1 - 16, 6*
dC 3rd Un-Occ. Set Back Time
.1, .5, 1 - 24, 3* (dA) - 24, 3*
dF Jace Group Code 00* - 99 00* - 99
r4 Room Prefix 00* - 99 00* - 99
r5 Room Suffix 00* - 99 00* - 99
*Indicates factory default
See manufacturer for additional configuration options.
Loading ...
Loading ...
Loading ...