OP ER A TION: Per for mance
Typical Low Side Pressure
· Air Cooled: 34 - 38 PSIG
Typical Discharge Pressure
· Air Cooled: 220 - 275 PSIG
Typical Compressor Amp Draw
· Single phase = 4.3
Superheat
· 5 - 7 degrees
High Pressure Cut Out - automatic reset
· 450 PSIG
Low Pressure Cut Out - automatic reset
· 15 PSIG
Refrigerant Charge (per system)
· Air Cooled: 30 ounces R-404A