CAUTION!
• Make sure cylinder valve is in its full o posion. (Turn clockwise to stop).
• Check cylinder valve features to ensure it has proper external mang threads. (Cylinder Valve
Marked: USE WITH TYPE 1)
• Inspect hose shipped with the unit for damage. Never aempt to use damaged or plugged
equipment. See your local LP Gas Dealer for repairs.
• When connecng regulator assembly to the cylinder valve, hand ghten black QCC1 nut clockwise
to a posive stop. DO NOT use a wrench to ghten. Use of a wrench may damage the quick closing
coupling nut and result in a hazardous condion.
• Locate the hose out of pathways where people may trip over it or in areas where the hose may be
subject to accidental damage.
• Open cylinder valve fully (counter-clockwise). Turn the on/o valve at the unit slowly to the on
posion and use a soapy water soluon to check all connecons for leaks as indicated in the
diagrams before aempng to light the appliance. If a leak is found, turn tank valve o and do not
use the appliance unl repairs can be made.
Enclosures For LP (Propane) Gas Supply Systems
If you build an enclosure for an LP gas cylinder, follow these recommended specicaons. You must also
follow local codes.
• An enclosure for an LP-gas cylinder shall be venlated by openings at both the upper and lower levels
of the enclosure.
This shall be accomplished by one of the following:
One side of the enclosure shall be completely open;
OR
For an enclosure having four sides, a top, and a boom:
a) At least two venlaon openings shall be provided in the sidewalls of the enclosure, located within 5 in
(127 mm) of the top of the enclosure, equally sized, spaced at a minimum of 90 degrees (1.57 rad), and
unobstructed. The opening(s) shall have a total free area of not less than 1 in
2
per lb (14.2 cm
2
/ kg) of
stored fuel capacity.
b) Venlaon opening(s) shall be provided at oor level of the enclosure and shall have a total free area of
not less than 1/2 in
2
per lb (7.1 cm
2
/ kg) of stored fuel capacity. If venlaon openings at oor level are in
a side wall, there shall be at least two openings. The boom of the openings shall be 1 in (25.4 mm) or less
from the oor level and the upper edge no more than 5 in (127 mm) above the oor level. The openings
shall be equally sized, spaced at a minimum of 90 degrees (1.57 rad), and unobstructed.
c) Every opening shall have minimum dimensions so as to permit the entrance of a 1/8 inch (3.2mm)
diameter rod.
Venlaon openings in sidewalls shall not communicate directly with other enclosures of the
appliance.
Cylinder valves shall be readily accessible for hand operaon. A door on the enclosure to gain access to the
cylinder valve is acceptable, provided it is non-locking and can be opened without the use of tools. Designs
using a cover to gain access to the cylinder and cylinder valve shall be provided with handles or
equivalent at a minimum of 180 degrees apart to facilitate liing of the cover.
There shall be a minimum clearance of 2 inches (50.8mm) between the lower surface of the oor of the LP
gas supply cylinder enclosure and the ground.