Make sure cylinder valve is in its full o posion. (Turn clockwise to stop).
Check cylinder valve features to ensure it has proper external mang threads. (Cylinder Valve
Marked: USE WITH TYPE 1)
Inspect hose shipped with the unit for damage. Never aempt to use damaged or plugged
equipment. See your local LP Gas Dealer for repairs.
When connecng regulator assembly to the cylinder valve, hand ghten black QCC1 nut clockwise
to a posive stop. DO NOT use a wrench to ghten. Use of a wrench may damage the quick closing
coupling nut and result in a hazardous condion.
Locate the hose out of pathways where people may trip over it or in areas where the hose may be
subject to accidental damage.
Open cylinder valve fully (counter-clockwise). Turn the on/o valve at the unit slowly to the on
posion and use a soapy water soluon to check all connecons for leaks as indicated in the
diagrams before aempng to light the appliance. If a leak is found, turn tank valve o and do not
use the appliance unl repairs can be made.
Enclosures For LP (Propane) Gas Supply Systems
If you build an enclosure for an LP gas cylinder, follow these recommended specicaons. You must also
follow local codes.
An enclosure for an LP-gas cylinder shall be venlated by openings at both the upper and lower levels
of the enclosure.
This shall be accomplished by one of the following:
One side of the enclosure shall be completely open;
OR
For an enclosure having four sides, a top, and a boom:
a) At least two venlaon openings shall be provided in the sidewalls of the enclosure, located within 5 in
(127 mm) of the top of the enclosure, equally sized, spaced at a minimum of 90 degrees (1.57 rad), and
unobstructed. The opening(s) shall have a total free area of not less than 1 in
2
per lb (14.2 cm
2
/ kg) of
stored fuel capacity.
b) Venlaon opening(s) shall be provided at oor level of the enclosure and shall have a total free area of
not less than 1/2 in
2
per lb (7.1 cm
2
/ kg) of stored fuel capacity. If venlaon openings at oor level are in
a side wall, there shall be at least two openings. The boom of the openings shall be 1 in (25.4 mm) or less
from the oor level and the upper edge no more than 5 in (127 mm) above the oor level. The openings
shall be equally sized, spaced at a minimum of 90 degrees (1.57 rad), and unobstructed.
c) Every opening shall have minimum dimensions so as to permit the entrance of a 1/8 inch (3.2mm)
diameter rod.
Venlaon openings in sidewalls shall not communicate directly with other enclosures of the
appliance.
Cylinder valves shall be readily accessible for hand operaon. A door on the enclosure to gain access to the
cylinder valve is acceptable, provided it is non-locking and can be opened without the use of tools. Designs
using a cover to gain access to the cylinder and cylinder valve shall be provided with handles or
equivalent at a minimum of 180 degrees apart to facilitate liing of the cover.
There shall be a minimum clearance of 2 inches (50.8mm) between the lower surface of the oor of the LP
gas supply cylinder enclosure and the ground.