LG Electronics ARWN048GA2

User Manual - Page 61

For ARWN048GA2.

PDF File Manual, 67 pages, Download pdf file

Loading ...
Loading ...
Loading ...
Test Run
ENGLISH
Installation Manual 61
Display Error item Root cause of error
5 3 1
Communication error with master outside
unit contrller and indoor unit
When the indoor uint control signal is not received from
the master outside unit inverter controller
5 7 1
Communication error between outside
unit inverter controller
Failing to receive inverter contoroller signal at Outdoor
Unit controller
6 0 1 Outside unit inverter PCB EEPROM error Oudoor unit inverter PCB EEPROM ACCESS error
6 2 1 Outside unit inverter IGBT over-rise error
Outside unit inverter IGBT when the temperature rises
above 110°C
6 5 1
Outside unit inverter IGBT temperature
sensor error
Outside unit inverter IGBT temperature sensor discon-
nection or short circuit
7 0 1 Outside unit static speed CT sensor error
Outside unit static speed CT sensor disconnection or
short circuit
7 1 1 PFC CT Sensor Error of Outdoor Unit Outdoor Unit PFC CT Sensor open or short
7 3 1
Outside unit inverter PCB input instant
over-current (Peak)
Outside unit inverter PCB input instant over-current
(Peak) exceeded
7 4 1
Outside unit inverter PCB phase imbal-
ance
When the master outside unit inverter PCB input current
is different
8 6 1 Outside unit master PCB EEPROM error
Communication error between master outside unit master
MICOM and EEPROM or EEPROM missing
8 8 1 PFC PCB EEPROM error
Communication error between Outside unit PFC and
EEPROM or EEPROM missing
1
1 3 1
Outside unit liquid pipe temperature sen-
sor error
Outside unit liquid pipe temperature sensor disconnection
or short circuit
1 5 1 1 Outside unit 4 way valve switch failure Outside unit 4 way valve switch error
1 8 0 1
Plate type heat exchanger freeze preven-
tion
Plate type heat exchanger freeze prevention error
1 8 1 1 Water temperature sensor error Water temperature sensor open/short
1 8 2 1 Communication error between MICOMs
Communication error between main MICOM and sub
MICOM
n Refer to the troubleshooting guide of service technical manual for each error.
Outside unit
Loading ...
Loading ...
Loading ...