This unit has many features. The servicer must be familiar with these features in order to properly service the unit.
Compressor Restart Delay
This feature extends the overall life of the compressor by preventing the shorting cycling of the air conditioner. When the compressor restarts, the unit is designed to give a minimum of three minutes to have a time of equalizing the refrigerant pressures for optimizing cycling.
Memory
The unit has memory. If power is lost, all of the control settings (mode, fan speed, on/off and configuration) are remembered. So when power is restored, the unit will start back up in the mode (and configuration) it was in, before power was lost.
Automatic Evaporator Freeze Protection
Automatically keeps the evaporator from freezing, the compressor is turned off and the indoor fan is turned on when the evaporator temperature is too low. If the evaporator temperature is not too low this function is off.
Automatic Quick Warm-up (for heat pump models only)
If the room temperature falls to 4.5°C/8°F below the set point temperature, the reverse cycle heat is shut off and the electric strip heat is turned on for one cycle, until the set temperature is satisfied.
LED Indicators and Buttons
The touch pad has buttons for MODE,FAN, POWER, SETPOINT UP and SETPOINT DOWN. It also has LEDs that correspond to the mode, fan speed, power, and set point operation to indicate the unit status. LEDs for HIGH, MED and LOW indicate the fan speed that is selected. LEDs for FAN, COOL and HEAT indicate what operating mode is active. LED for POWER is the unit ON/OFF status LED. If the unit is in ON mode, the LED will be green. If the unit is OFF, the LED will be off.
High Temperature Protection In Heating Operation
The compressor and (or) electric heater will be switched off to prevent damage in high indoor blow air temperature or error indoor temperature sensor.
Temperature Display Configuration(°F or °C)
The unit can display in either °F or °C.
The control panel keypad will look like the following Fig. 1. For some models with REMOTE SIGNAL RECEPTOR, the unit can be controlled by the control panel alone or by the remote.

POWER
Press the POWER button to turn the unit on or off. When the unit is on, the power indicator light will be green. When the unit is off, the light will go out.
MODE
Push this button to cycle through the modes from COOL-HEAT-FAN-COOL.The indicator light beside the “MODE” option will illuminate, identifying the mode selected.
NOTES
The reverse cycle and electric heater cannot be ran at the same time. In following cases, it is normal that the reverse cycle does not operate.
UP/DOWN BUTTONS ( + / - )
Push the UP (or DOWN) button to increase (or decrease) the set temperature of the unit in cooling or heating mode. The temperature can be set by increments of 1° F (1°C). The setting temperature appears in the display.
FAN (FAN SPEED)
Every time you push this button, the fan speed cycles through the settings as follows: HIGH-MED-LOW-HIGH.
DISPLAYS:
Shows the set temperature in °C or °F.While on Fan only mode, it shows the room temperature.
Control code (on some models):
LC - Control panel operation not available.The unit can be controlled by using Wired Wall Thermostat only.
FC - Pads on the control panel and wire controller are not available. The unit can be setted by using FRONT DESK CONTROL only.
Error codes:
AS - Room temperature sensor error
ES - Evaporator temperature sensor error
CS - Condenser temperature sensor error
OS - Outside temperature sensor error
HS - Exhaust temperature sensor error
LE - Wire controller error
Other codes:
LO - Room temperature is lower than 0°C/32°F;
HI - Room temperature is higher than 37°C/99°F;
FP - Low temperature protection.

REMOVING THE FRONT PANEL


DIP SWITCHES CONFIGURATIONS
See Table 1 and Fig. 4 for Dip Switches configurations and functions of each dip switch position.


Wall Thermostat Enable
A wired wall thermostat can be connected to the unit. If it is, this dip switch must be moved to the Wall Thermostat Enable Position, before the wall thermostat will begin control.
Low temperature protecton (optional)
If unit senses a room temperature below 32°F (0°C), the fan motor and electric strip heat will turn on and warm the room to 40°F (4.4°C). The fan stops a short time after the temperature is satisfied.
Electric Heat Only (for heat pump unit only)
This setting is typically used for Emergency Heating.
Setpoint Temperature Limits
Provides a restricted range of temperature control.
Heat and Cool Fan CON/CYC Dip-switches
Allows the fan to operate in continuous or cycle modes while the unit is in heating and cooling mode.
Allows fan to run continuously, circulating air even when the temperature setting has been satisfied. This switch helps to maintain the room temperature closer to the thermostat setting.
This setting allows the fan to cycle on and off with the compressor or electric heater. The fan stops a short time after the temperature setting is satisfied.


NOTE
1. The LED display window will show 00 when you first enter the setting mode, only when you set 01, can you start the next settings.
2. To activate front desk control function, you need to pull the dip switch SW7 to DOWN (OFF), and then set the panel control to “A0”.
3. After all switches have been set, press up (+) and down (-) buttons together for 3 seconds to exit the operation interface and cut off the power. When re-power on, the settings are activated.
Thermostat Wire Routing
Thermostat wire is field supplied. Recommended wire gauge is 18 to 20 gauge solid thermostat wire.
NOTE It is recommended that extra wires are run to unit in case any are damaged during installation. Thermostat wire should always be routed around or under, NEVER through, the wall sleeve. The wire should then be routed behind the front panel to the easily accessible terminal connector

Wired Wall Thermostat Connection Instructions
Remove the two screws as shown below and take the cover panel down to enable wall thermostat

NOTES
FRONT DESK CONTROL
The controller can handle a switch signal from FC (L) and FC (N) input, called front desk control. Input must be 24VAC. If system doesn’t receive a 24VAC signal, it will turn the unit off; otherwise, the unit runs in normal control.

HOW TO INSTALL THE UNIT

PREPARATION OF SLEEVE ASSEMBLY (optional)
Refer to the installation instruction of sleeve assembly for details.
PREPARATION OF REAR GRILLE ASSEMBLY (optional)
Refer to the installation instruction of rear grille assembly for details.
UNIT INSTALLATION






FRONT PANEL AND CASE
Turn unit off and disconnect power supply.
To clean, use water and a mild detergent. DO NOT use bleach or abrasives. Some commercial cleaners may damage the plastic parts.
OUTDOOR COIL
Coil on outdoor side of unit should be checked regularly. Unit will need to be removed to inspect dirt build-up that will occur on the inside of the coil.If clogged with dirt and soot, coil should be professionally cleaned of debris. Clean inside and outside of outdoor coils regularly.
AIR FILTERS
The most important thing you can do to maintain unit efficiency is to clean the filters once every two weeks as required. Clogged filters reduce cooling, heating and airflow.
Keeping filters clean will:
To Clean Air Filters:

VENT DOOR FILTER

| POSSIBLE CAUSES | SOLUTIONS |
|---|---|
|
UNIT DOES NOT START
|
Note: Plug has a test/reset button on it. Make sure that the plug has not tripped.
|
|
UNIT NOT COOLING/HEATING ROOM
Note: Setpoint limits may not allow the unit to heat or cool the room to the temperature desired. Check section on dipswitch settings.
|
|
| DISPLAY HAS STRANGE NUMBERS / CHARACTERS ON IT |
|
| UNIT MAKING NOISES | Clicking, gurging and whooshing noises are normal during operation of unit. |
| WATER DRIPPING OUTSIDE | If a drain kit has not been installed, condensation runoff during very hot and humid weather is normal. See Note 2. If a drain kit has been installed and is connected to a drain system, check gaskets and fittings around drain for leaks and plugs. |
|
WATER DRIPPING INSIDE
|
Wall sleeve must be installed level for proper drainage of condensation. Check that installation is level and make any necessary adjustments. |
|
ICE OR FROST FORMS ON INDOOR COIL
|
|
|
COMPRESSOR PROTECTION Power may have cycled, so compressor is in a restart protection. |
|
| ELECTRIC HEATING FAILURE | Clean the evaporator twice yearly by qualified personnel |
NOTES
1. If circuit breaker is tripped or fuse is blown more than once, contact a qualified electrician.
2. If unit is installed where condensation drainage could drip in an undesirable location, an accessory drain kit should be installed and connected to drain system.
Reference file: Pelonis PP12HMB82 12,000 BTU 230-Volt Packaged Terminal Air Conditioner
Additionally, the document applies to other Pelonis models: PP09HMB82, PP15HMB82