82
TEST RUN
ENGLISH
Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using
duct at fan discharge of ODU.
Static pressure compensation mode setting method
FAN Maximum RPM of each step (460V Model)
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn2” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1~op3” Push the ‘’ button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
Capacity 8HP(6Ton)
10~14HP,18HP(8~14Ton)
Max. RPM
Standard 730 950
op1 760 1020
op2 780 1050
op3 800 1130
FAN Maximum RPM of each step (220V Model)
Capacity 8HP(6Ton)
10~14HP,18HP(8~14Ton)
Max. RPM
Standard 850 1050
op1 870 1080
op2 890 1110
op3 900 1120