OUTDOOR UNITS INFORMATION
13
ENGLISH
Model Name : ARUN***DTE4
Power Supply Outdoor Unit (3Ø, 460V, 60Hz)
Chassis
UX3 UX3
HP
14 18
Ton
12 14
Model Name
Combination Unit
ARUN144DTE4 ARUN168DTE4
Independent Unit
Refrigerant
Refrigerant name
R410A R410A
Control
EEV EEV
Number of maximum connectable indoor units
23 29
Net Weight
kg
(285 × 1) (285 × 1)
lbs
(628 × 1) (628 × 1)
Pipe
Connections
Liquid Pipes mm(inch)
12.7(1/2) 15.88(5/8)
Low Pressure Gas Pipes
mm(inch)
28.58(1 1/8) 28.58(1 1/8)
Chassis
UX2 UX3 UX3
HP
8 10 12
Ton
6 8 10
Model Name
Combination Unit
ARUN072DTE4 ARUN096DTE4 ARUN121DTE4
Independent Unit
Refrigerant
Refrigerant name
R410A R410A R410A
Control
EEV EEV EEV
Number of maximum connectable indoor units
13 16 20
Net Weight
kg
(195 × 1) (245 × 1) (245 × 1)
lbs
(430 × 1) (540 × 1) (540 × 1)
Pipe
Connections
Liquid Pipes mm(inch)
9.52(3/8) 9.52(3/8) 12.7(1/2)
Low Pressure Gas Pipes
mm(inch)
19.05(3/4) 22.2(7/8) 28.58(1 1/8)