28 Multi zone
Installation
Installer Setting - E.S.P.
Static pressure(mmAq)
Setting value
01234
Model name
Step(H/M/L)
9.5 CMM(335cfm) 82 90 99 109 118
8.5 CMM(300cfm) 75 84 94 104 114
7.5 CMM(265cfm) 69 77 88 99 110
15 CMM(530cfm) 90 97 105 114 122
13.5 CMM(477cfm) 82 90 99 109 119
11.5 CMM(406cfm) 75 84 93 103 114
MD12Y3JM
MD18Y3JM
This is the function that decides the strength of the wind for each wind level and because this
function is to make the installation easier.
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
TEMP
FAN
SPEED
OPER
MODE
When pressing the button and button
simultaneously for more than 3 seconds, the system will be
entered into the installer setting mode.
- After entering into the installer setting mode, select the
E.S.P code value by pressing the button.
* E.S.P code value : 03
1
Select the desired air flow rate with
the button. Whenever pressing
the button, [SLo
Lo
Med
Hi
Po] will be indicated.
2
Select the desired air flow rate value with the temperature
up(), down() button.
* E.S.P value range : 0~255
-
E.S.P value will be indicated at the upper right section of the
display window.
3
When pressing the button, currently established E.S.P
value will be set up.
4
When pressing the button and button simultaneously
for more than 3 seconds after the setting has been completed,
the setting mode will be released.
- If there isn’t any button input for more than 25 seconds, the
installer setting mode will also be released.
5
OPER
MODE
OPER
MODE
FAN
SPEED
FAN
SPEED
OPER
MODE