Part Number 000015236 Rev 00 11/17 9
Location of Ice Machine
The location selected for the ice machine must meet the
following criteria. If any of these criteria are not met, select
another location.
The location must be free of airborne and other
contaminants.
This equipment is intended for indoor use only. Do not
install or operate this equipment in outdoor areas.
The air temperature must be at least 50°F (10°C), but
must not exceed 110°F (43°C).
The water temperature must be at least 37°F (3°C), but
must not exceed 90°F (32°C).
The location must not be near heat-generating
equipment or in direct sunlight.
The location must be capable of supporting the weight of
the ice machine and a full bin of ice.
The location must allow enough clearance for water,
drain and electrical connections in the rear of the ice
machine.
The location must not obstruct airflow through or around
the ice machine.
CLEARANCE REQUIREMENTS
Undercounter Units Air-Cooled Water-Cooled
Top 0" (0 cm) 0" (0 cm)
Sides 2" (5 cm) 2" (5 cm)
Back 8" (20 cm) 8" (20 cm)
NOTE: Allowance must be made for removal when the ice machine is built in. Removal
of the top panel is required for cleaning & sanitizing.
Modular Units
Air-
Cooled
Water-
Cooled
QuietQube
Air-Cooled
Top/Sides 8" (20 cm) 8" (20 cm) 0" (0 cm)
Back 5" (13 cm) 5" (13 cm) 0" (0 cm)
RCUF Units Remote Condensing Unit
Front/Back 24" (61 cm)
Sides/Top 6" (15.2 cm)
Installation Requirements
The ice machine and bin must be level.
Install the bin drain and ice machine drain separately.
Ice machine drain must be vented.
Bin drain termination must have an air gap.
When local requires a backflow preventer must be
installed on water inlet lines.
The ice machine and bin must be sanitized after
installation.
Local water conditions may require treatment of the
water to inhibit scale formation, filter sediment, and
remove chlorine odor and taste.
Routine adjustments and maintenance procedures
outlined in this manual are not covered by the warranty.
Ice Machine Heat of Rejection
Series
Ice Machine
Heat of Rejection
A/C Btuh
Heat of Rejection
Peak Btuh
UFF0200 RFF0320 2400 5000
RNF0320 3075 4100
RFF0620 - RNF0620 5200 7700
RNF1100 7500 10900
RFF1300 7500 14000
RFF2500 17000 29500
Ice machines, like other refrigeration equipment, reject heat
through the condenser. It is helpful to know the amount of
heat rejected by the ice machine when sizing air conditioning
equipment.
This information is also necessary when evaluating the
benefits of using water-cooled or remote condensers to
reduce air conditioning loads. The amount of heat added to
an air conditioned environment by an ice machine using a
water-cooled or remote condenser is negligible.
Knowing the amount of heat rejected is also important when
sizing a cooling tower for a water-cooled condenser. Use the
peak figure for sizing the cooling tower.
Section 2
Installation Instructions